CBECC-Com Issue - Lighting/Internal Loads #870

Closed GoogleCodeExporter closed 9 years ago

GoogleCodeExporter commented 9 years ago

Version = 2013_3_653

Category = Lighting/Internal Loads

Issue Summary:
List the steps taken to produce the error. For example:
      1. step 1 – open the file
      2. step 2 – click calculate
      3. step 3 – software produces error message:

In an effort to create a Prescriptive i.e. neutral model, I increased the 
wattage of my light fixture…but this caused the above error. It seems to 
occur if you have more than 120 W of lighting total within the Primary Daylight 
Zone…whether or not you add controls!

Original issue reported on code.google.com by f.le...@gmail.com on 5 Dec 2014 at 9:35

Attachments:

GoogleCodeExporter commented 9 years ago
On the Daylighting tab of the Space Data input screen, you do not have any 
daylighting controls turned on.  For nonresidential spaces, if there is more 
than 120 W of lighting power in the primary sidelit or skylit daylighting 
areas, daylighting controls are mandatory.  You can resolve this error by 
checking the “100% controlled” box, as shown below.

Original comment by rhedr...@archenergy.com on 5 Dec 2014 at 10:45