on 18 Dec 2014 at 9:32
This is being addressed in rule updates today.
Original comment by da...@360-analytics.com
on 18 Dec 2014 at 9:35
For systems, the default is now set to be max( 55F, zone cooling design SAT).
The zone cooling design SAT is specified to be 20F below the minimum value
specified in the cooling thermostat schedule. Using the default schedules, the
min value is 75F, which results in a 55F zone design SAT.
Original comment by da...@360-analytics.com
on 25 Jan 2015 at 9:59