kbenne / cbecc

Automatically exported from code.google.com/p/cbecc
0 stars 0 forks source link

Title 24 Nonres ACM - Fan Motor Efficiency #913

Closed GoogleCodeExporter closed 9 years ago

GoogleCodeExporter commented 9 years ago
Table 29 in the Nonresidential Alternative Calculation Method manual shows the 
minimum nominal efficiency for electric motors. I was wondering where in the 
Standards this table was drawn from? The most relevant section I could find is 
140.4(c).

Original issue reported on code.google.com by f.le...@gmail.com on 21 Jan 2015 at 10:42

GoogleCodeExporter commented 9 years ago
140.4(c) has requirements only for fractional hp motors. The requirements come 
from NEMA Standard MG1-2007.  There is no explicit requirement in Title 24 Part 
6 for motor efficiency of motors 1 hp and greater.

Original comment by JohnJArent on 27 Jan 2015 at 11:48

GoogleCodeExporter commented 9 years ago

Original comment by rhedr...@archenergy.com on 20 Feb 2015 at 4:54