CBECC-Com Issue - HVAC #914

Open GoogleCodeExporter opened 9 years ago

GoogleCodeExporter commented 9 years ago
Version = 2013_3_653

Category = HVAC

Issue Summary:
I’m trying to model a building with single zone VAV units (8 per floor). 
I’m using the uncontrolled boxes as mentioned in the FAQ. Somehow my baseline 
model uses less heating energy than my proposed model. I ran the .idf file in 
energyplus to generate hourly reports. In the attached csv file if you look at 
columns H and I, the zone ZN F-40_Z1 temperature seems to overshoot above the 
heating setpoint. The system seems to kind of work but the control doesn’t 
seem to be accurate. I changed the systems to be with VAV reheat boxes and kept 
the heating coils only at the boxes, with an aggressive SAT reset at the system 
level to avoid any “reheat”. In that case my proposed model heating energy 
went down and looking at the hourly report the zone temperatures are better 
controlled to setpoint. Am I missing something in my model with uncontrolled 
boxes or should I be using the VAVRH boxes?

Original issue reported on code.google.com by f.le...@gmail.com on 21 Jan 2015 at 10:43