1. Hotel Motel Function Area shows 67 occ/1000SF but NonRes Compliance Manual
Table 4-14 shows it to be 143 occ/1000 SF.
2. Hotel Motel Function Area shows ventilation at 0.50 CFM/SF but Table 4-14
shows it to be 1.07 CFM/SF.
3. Bar, Cocktail Lounge shows ventilation at 0.20 CFM/SF but Table 4-14 shows
it to be 0.50 CFM/SF.
4. Retail, Wholesale shows ventilation at 0.20 CFM/SF but Table 4-14 shows it
to be 0.25 CFM/SF
Original issue reported on code.google.com by thaochau8 on 24 Jan 2015 at 12:04
Original issue reported on code.google.com by
thaochau8