Wrong minimum values in some space function areas #919

Open GoogleCodeExporter opened 9 years ago

GoogleCodeExporter commented 9 years ago
1.  Hotel Motel Function Area shows 67 occ/1000SF but NonRes Compliance Manual 
Table 4-14 shows it to be 143 occ/1000 SF.
2.  Hotel Motel Function Area shows ventilation at 0.50 CFM/SF but Table 4-14 
shows it to be 1.07 CFM/SF.
3.  Bar, Cocktail Lounge shows ventilation at 0.20 CFM/SF but Table 4-14 shows 
it to be 0.50 CFM/SF.
4.  Retail, Wholesale shows ventilation at 0.20 CFM/SF but Table 4-14 shows it 
to be 0.25 CFM/SF

Original issue reported on code.google.com by thaochau8 on 24 Jan 2015 at 12:04

GoogleCodeExporter commented 9 years ago
[deleted comment]
GoogleCodeExporter commented 9 years ago
Corrected in the Appendix 3.4A SpaceUseData file

Original comment by thaochau8 on 5 Feb 2015 at 4:00