AirSystem 1 has a cfm/ton which is out of bound as per Energy Plus
calculations. The details of the error message are below:
1: Sizing: Coil:Cooling:DX:SingleSpeed "COILCOOLING 1": Rated air volume flow
rate per watt of rated total cooling capacity is out of range.
Min Rated Vol Flow Per Watt=[4.027E-005], Rated Vol Flow Per Watt=[6.688E-006], Max Rated Vol Flow Per Watt=[6.041E-005]. See Input Output Reference Manual for valid range.
- 2: For object = Coil:Cooling:DX:SingleSpeed, name = "COILCOOLING 1"
Calculated outlet air relative humidity greater than 1. The combination of
rated air volume flow rate, total cooling capacity and sensible heat ratio yields coil exiting
air conditions above the saturation curve. Possible fixes are to reduce the rated total cooling
capacity, increase the rated air volume flow rate, or reduce the rated sensible heat ratio for this coil.
This error can be corrected by either reducing the cooling capacity or
increasing the system air flow.
Other issues in the model include:
1. No heating coil in AirSystem 2,3,4,5,6,7,8,9,10
2. No cooling coil in AirSystem 2,3,4,5,6,7,8,9,10
Please include a heating and cooling coil on the supply segment of each of
these systems.