Sunsynk/Deye Inverter Add-on (edge/dev) bc65f2a does not read any values, but gives errors #311

Open bsafh opened 3 days ago

bsafh commented 3 days ago

Issue related to

Sunsynk/Deye Inverter Add-on (edge/dev) Current version: bc65f2a

Describe the issue/bug

gives error on startup

Expected behavior continue to read values

Your environment

You configuration


DRIVER: pymodbus
INVERTERS:
  - SERIAL_NR: "2312122xxx"
    HA_PREFIX: WR_Deye_1
    MODBUS_ID: 1
    DONGLE_SERIAL_NUMBER: "0"
    PORT: serial-tcp://192.168.80.44:8234
  - SERIAL_NR: "2312126yyy"
    HA_PREFIX: WR_Deye_2
    MODBUS_ID: 2
    DONGLE_SERIAL_NUMBER: "0"
    PORT: serial-tcp://192.168.80.45:8234
SENSOR_DEFINITIONS: three-phase-hv
SENSORS:
  - energy_management
  - power_flow_card
  - pv2_power
  - settings
  - all
  - pv1_power
  - essential_power
  - battery_power
  - battery_soc
  - non_essential_power
  - grid_ct_power
  - Inverter power
  - Inverter L1 power
  - Inverter L2 power
  - Inverter L3 power
  - Inverter voltage
  - Inverter frequency
  - Grid frequency
  - Grid power
  - Grid L1 power
  - Grid L3 power
  - Grid L2 power
  - Grid L2 voltage
  - Grid L1 voltage
  - Grid L3 voltage
  - Load power
  - Load L1 power
  - Load L2 power
  - Load L3 power
  - Load L1 voltage
  - Load L2 voltage
  - Load L3 voltage
  - PV1 power
  - PV1 voltage
  - PV1 current
  - PV2 power
  - PV2 voltage
  - PV2 current
  - Gen power
  - Gen L1 power
  - Gen L2 power
  - Gen L3 power
  - Gen Energy
  - Load Energy
  - Total Load Energy
  - Rated power
  - Device type
  - Fault
  - Overall state
  - Serial
  - DC transformer temperature
  - Radiator temperature
  - Grid Connected
  - Date Time
  - INV Relay Status
  - Undefined Load Relay Status
  - Grid Relay Status
  - Generator Relay Status
  - Grid Give Power to Relay Status
  - Dry Contact1 Status
  - Dry Contact2 Status
  - Grid Charge Battery current
  - Grid Charge Start Battery SOC
  - Grid Charge enabled
  - Use Timer
  - Solar Export
  - Export Limit power
  - Battery Max Charge current
  - Battery Max Discharge current
  - Battery Capacity current
  - Grid Peak Shaving power
  - Battery low voltage
  - System Zero Export power
  - Battery Equalization Days
  - Battery Equalization Hours
  - Generator Charge enabled
  - Battery Wake Up
  - Battery Resistance
  - Generator Port Usage
  - Battery Equalization voltage
  - Battery Absorption voltage
  - Battery Float voltage
  - Battery Shutdown Capacity
  - Battery Restart Capacity
  - Battery Low Capacity
  - Battery Shutdown voltage
  - Battery Low voltage
  - Battery Restart voltage
  - Priority Load
  - Load Limit
  - Prog1 Time
  - Prog2 Time
  - Prog3 Time
  - Prog4 Time
  - Prog5 Time
  - Prog6 Time
  - Prog1 power
  - Prog2 power
  - Prog3 power
  - Prog4 power
  - Prog5 power
  - Prog6 power
  - Prog1 Capacity
  - Prog2 Capacity
  - Prog3 Capacity
  - Prog4 Capacity
  - Prog5 Capacity
  - Prog6 Capacity
  - Prog1 charge
  - Prog2 charge
  - Prog3 charge
  - Prog4 charge
  - Prog5 charge
  - Prog6 charge
  - Prog1 mode
  - Prog2 mode
  - Prog3 mode
  - Prog4 mode
  - Prog5 mode
  - Prog6 mode
  - Prog1 voltage
  - Prog2 voltage
  - Prog3 voltage
  - Prog4 voltage
  - Prog5 voltage
  - Prog6 voltage
  - Day Active Energy
  - Day Battery Charge
  - Day Battery discharge
  - Day Grid Export
  - Day Grid Import
  - Day Gen Energy
  - Day Load Energy
  - Day PV Energy
  - Total Active Energy
  - Total Battery Charge
  - Total Battery Discharge
  - Total Grid Export
  - Total Grid Import
  - Total PV Energy
  - Battery temperature
  - Battery voltage
  - Battery SOC
  - Battery power
  - Battery current
  - Battery Charge Limit current
  - Battery Discharge Limit current
  - Inverter current
  - Grid LD power
  - Grid voltage
  - Grid current
  - Grid CT power
  - Load frequency
  - AUX power
  - Essential power
  - Essential 1 power
  - Essential 2 power
  - Non-Essential power
  - Day Battery Discharge
  - Day Reactive Energy
  - Month Grid Energy
  - Month Load Energy
  - Month PV Energy
  - Year Grid Export
  - Year Load Energy
  - Year PV Energy
  - Device Type
  - Overall State
  - Environment temperature
  - Control Mode
  - Generator input
  - Battery charging voltage
  - Bat1 SOC
  - Bat1 Cycle
  - Battery 1 temperature
  - Battery 1 voltage
  - Battery 1 SOC
  - Battery 1 power
  - Battery 1 current
  - A Phase Power on the Inner Side of the Grid
  - B Phase Power on the Inner Side of the Grid
  - C Phase Power on the Inner Side of the Grid
  - Total Active Power from Side to Side of the Grid
  - Grid Side - Inside Total Apparent Power
  - PV power
  - Gen L1 volts
  - Gen L2 volts
  - Gen L3 volts
  - Fan Warning
  - Grid Phase Warning
  - Lithium Battery Loss Warning
  - Parallel Communication Quality Warning
  - SD Status
  - Max Solar power
  - Generator Charge Start Battery SOC
  - Generator Charge Battery current
  - Parallel Battery 1 and 2
  - Battery 1 Wake Up
  - Battery Charge Efficiency
  - Battery Type
  - Prog Time Of Use Enabled
  - Prog Monday Enabled
  - Prog Tuesday Enabled
  - Prog Wednesday Enabled
  - Prog Thursday Enabled
  - Prog Friday Enabled
  - Prog Saturday Enabled
  - Prog Sunday Enabled
  - Gen peak-shaving
  - Grid peak-shaving
  - External relay
  - Loss of lithium battery report fault
  - DRM
  - Generator AC Couple Frz High
  - Generator Off SOC
  - Generator On SOC
  - Generator Max Operating Time
  - Generator Cooling Time
  - Min PV Power for Gen Start
  - Grid Signal On
  - Gen Signal On
  - Grid Standard
  - Configured Grid Frequency
  - Configured Grid Phases
  - Lithium HV BMS Protocol
  - Battery 1 Manufacturer
  - Battery 1 BMS charging voltage
  - Battery 1 BMS discharging voltage
  - Battery 1 BMS charging current limit
  - Battery 1 BMS discharging current limit
  - Battery 1 BMS SOC
  - Battery 1 BMS voltage
  - Battery 1 BMS current
  - Battery 1 BMS temperature
  - Battery 1 BMS max charge current limit
  - Battery 1 BMS max discharge current limit
  - Battery 1 BMS alarm flag
  - Battery 1 BMS fault flag
  - Battery 1 BMS other flag - Battery 1 Force charge
  - Battery 1 BMS other flag - Battery 2 Force charge
  - Battery 1 BMS other flag - Battery 1 Sleep
  - Battery 1 BMS type
  - Battery 1 BMS SOH
  - Battery 1 BMS software version
  - Battery 1 BMS rated AH
  - Battery 1 BMS hardware version
  - Time synchronization
  - Beep
  - AM PM
  - Auto dim
  - priority_mode
  - battery_temperature
  - battery voltage
  - battery_current
SENSORS_FIRST_INVERTER: []
MANUFACTURER: Deye
READ_ALLOW_GAP: 2
READ_SENSORS_BATCH_SIZE: 20
SCHEDULES:
  - KEY: w
    READ_EVERY: 5
    REPORT_EVERY: 10
    CHANGE_ANY: false
    CHANGE_BY: 50
    CHANGE_PERCENT: 1
  - KEY: kwh
    READ_EVERY: 60
    REPORT_EVERY: 120
    CHANGE_ANY: false
  - KEY: date_time
    READ_EVERY: 60
    REPORT_EVERY: 60
    CHANGE_ANY: true
  - KEY: rw
    READ_EVERY: 5
    REPORT_EVERY: 30
    CHANGE_ANY: true
  - KEY: any_unit
    READ_EVERY: 10
    REPORT_EVERY: 120
    CHANGE_ANY: false
  - KEY: no_unit
    READ_EVERY: 10
    REPORT_EVERY: 60
    CHANGE_ANY: true
NUMBER_ENTITY_MODE: box
PROG_TIME_INTERVAL: 15
MQTT_HOST: core-mosquitto
MQTT_PORT: 1883
MQTT_USERNAME: mqttuser
MQTT_PASSWORD: secret

Logs


14:20:14 INFO    Report every (inverter >1)
+-----+----------------------------------------------------------------------------------+
|  s  |                                     Sensors                                      |
+-----+----------------------------------------------------------------------------------+
|  10 |     load_l1_power, grid_ct_power, load_power, load_l3_power, grid_l1_power,      |
|     |       pv1_power, a_phase_power_on_the_inner_side_of_the_grid, grid_power,        |
|     |                 grid_l3_power, inverter_l3_power, grid_l2_power,                 |
|     |    b_phase_power_on_the_inner_side_of_the_grid, gen_power, inverter_l2_power,    |
|     | total_active_power_from_side_to_side_of_the_grid, load_l2_power, inverter_power, |
|     |         gen_l2_power, pv_power, grid_side___inside_total_apparent_power,         |
|     | inverter_l1_power, c_phase_power_on_the_inner_side_of_the_grid, battery_1_power, |
|     |                      gen_l1_power, gen_l3_power, pv2_power                       |
|  30 |  battery_1_bms_other_flag___battery_2_force_charge, grid_standard, prog5_power,  |
|     |      am_pm, battery_low_capacity, beep, prog_thursday_enabled, prog6_power,      |
|     | max_solar_power, prog3_capacity, battery_wake_up, battery_equalization_voltage,  |
|     |   load_limit, prog1_time, prog1_charge, prog5_charge, configured_grid_phases,    |
|     |            prog5_voltage, parallel_battery_1_and_2, gen_peak_shaving,            |
|     |     generator_ac_couple_frz_high, battery_equalization_days, prog1_voltage,      |
|     |   prog_wednesday_enabled, prog4_time, min_pv_power_for_gen_start, prog5_time,    |
|     |           grid_charge_start_battery_soc, grid_signal_on, prog3_power,            |
|     | generator_max_operating_time, battery_1_bms_other_flag___battery_1_force_charge, |
|     | external_relay, system_zero_export_power, prog4_charge, generator_cooling_time,  |
|     |                    prog_tuesday_enabled, prog_monday_enabled,                    |
|     |     battery_1_bms_other_flag___battery_1_sleep, battery_absorption_voltage,      |
|     |        prog_saturday_enabled, prog4_capacity, battery_equalization_hours,        |
|     |      battery_capacity_current, battery_float_voltage, battery_low_voltage,       |
|     |       prog3_voltage, grid_charge_enabled, generator_on_soc, solar_export,        |
|     |        generator_off_soc, prog2_charge, export_limit_power, prog6_charge,        |
|     |      gen_signal_on, prog4_voltage, prog1_capacity, battery_restart_voltage,      |
|     |  prog2_capacity, prog_sunday_enabled, generator_charge_enabled, priority_load,   |
|     |       grid_peak_shaving_power, prog3_charge, prog4_power, prog5_capacity,        |
|     |  battery_max_discharge_current, drm, prog6_voltage, battery_shutdown_capacity,   |
|     |    generator_charge_start_battery_soc, prog2_power, lithium_hv_bms_protocol,     |
|     |           generator_charge_battery_current, battery_shutdown_voltage,            |
|     |        grid_charge_battery_current, battery_max_charge_current, auto_dim,        |
|     | prog2_voltage, battery_restart_capacity, battery_1_wake_up, battery_resistance,  |
|     |     loss_of_lithium_battery_report_fault, generator_port_usage, prog3_time,      |
|     |          prog6_capacity, time_synchronization, use_timer, battery_type,          |
|     |    prog_time_of_use_enabled, prog_friday_enabled, configured_grid_frequency,     |
|     |              prog1_power, prog2_time, prog6_time, grid_peak_shaving              |
|  60 |           overall_state, battery_1_bms_alarm_flag, grid_relay_status,            |
|     |       generator_relay_status, grid_give_power_to_relay_status, sd_status,        |
|     |   undefined_load_relay_status, dry_contact1_status, battery_1_bms_fault_flag,    |
|     | battery_1_bms_type, dry_contact2_status, battery_1_bms_software_version, fault,  |
|     |   inv_relay_status, date_time, grid_connected, battery_1_bms_hardware_version    |
| 120 |              total_battery_charge, day_gen_energy, load_l2_voltage,              |
|     |   battery_1_bms_discharging_voltage, day_battery_charge, total_active_energy,    |
|     |   total_battery_discharge, battery_1_bms_charging_current_limit, pv1_voltage,    |
|     |            total_load_energy, grid_l2_voltage, day_battery_discharge,            |
|     |     battery_1_bms_max_charge_current_limit, inverter_frequency, pv1_current,     |
|     | day_active_energy, gen_l2_volts, day_pv_energy, grid_frequency, load_l3_voltage, |
|     |      gen_l1_volts, battery_1_bms_max_discharge_current_limit, pv2_voltage,       |
|     |            battery_1_bms_rated_ah, day_grid_import, grid_l3_voltage,             |
|     |    dc_transformer_temperature, pv2_current, total_pv_energy, day_load_energy,    |
|     | grid_current, battery_1_voltage, battery_1_soc, battery_1_bms_soc, gen_l3_volts, |
|     |   battery_charge_efficiency, battery_1_bms_temperature, radiator_temperature,    |
|     |  battery_1_bms_soh, load_l1_voltage, battery_1_bms_voltage, total_grid_export,   |
|     |  inverter_voltage, battery_1_bms_discharging_current_limit, total_grid_import,   |
|     |     battery_1_temperature, battery_1_bms_charging_voltage, grid_l1_voltage,      |
|     |            battery_1_bms_current, battery_1_current, day_grid_export             |
| 300 |                    lithium_battery_loss_warning, fan_warning,                    |
|     |     parallel_communication_quality_warning, device_type, grid_phase_warning,     |
|     |                              battery_1_manufacturer                              |
+-----+----------------------------------------------------------------------------------+
14:20:15 ERROR   NotImplementedError in read_wr_deye_2: 
14:20:15 ERROR   NotImplementedError in read_wr_deye_1: 
14:25:00 ERROR   (28 in 5 min) NotImplementedError in read_wr_deye_2: 
14:25:00 ERROR   (28 in 5 min) NotImplementedError in read_wr_deye_1: 
14:30:00 ERROR   (30 in 5 min) NotImplementedError in read_wr_deye_2: 
14:30:00 ERROR   (30 in 5 min) NotImplementedError in read_wr_deye_1: 
bsafh commented 3 days ago

See also https://github.com/kellerza/sunsynk/commit/bc65f2a796e556fcd86fb309f6c6b9fd20934ce9

kellerza commented 2 days ago

NotImplementedError was a bug introduced in e353fc60cf7b21510be69258a794a8ab531c11fd. Should be fixed in 3a882cd71ecfd7d4ceec85ef2ad36c5df0fbdd5d (with some better error logs)

Update the dev/edge addon to at least version 2cec340 (latest build that include device_type for single phase inverters)

bsafh commented 2 days ago

Update the dev/edge addon to at least version 2cec340 (latest build that include device_type for single phase inverters)

done

seems to start up fine

|    |     configured_grid_frequency, external_relay, battery_wake_up, prog6_time,      |
|    |        battery_shutdown_capacity, gen_peak_shaving, prog_friday_enabled,         |
|    |        inverter_l1_power, solar_export, prog_tuesday_enabled, load_limit,        |
|    |         load_l1_power, generator_charge_battery_current, grid_l1_power,          |
|    |      c_phase_power_on_the_inner_side_of_the_grid, prog_time_of_use_enabled,      |
|    |            prog2_time, battery_max_discharge_current, prog1_capacity,            |
|    | lithium_hv_bms_protocol, prog5_time, grid_peak_shaving, battery_1_manufacturer,  |
|    |    device_type, b_phase_power_on_the_inner_side_of_the_grid, battery_1_power,    |
|    |      battery_type, am_pm, generator_off_soc, generator_on_soc, prog5_power,      |
|    |       prog1_voltage, gen_l3_power, priority_load, grid_peak_shaving_power,       |
|    |               prog3_capacity, beep, grid_standard, load_l2_power,                |
|    | battery_1_bms_other_flag___battery_2_force_charge, generator_max_operating_time, |
|    |    prog1_power, pv1_power, grid_ct_power, grid_charge_enabled, gen_l2_power,     |
|    |    battery_low_capacity, prog4_charge, load_power, generator_charge_enabled,     |
|    |                            battery_absorption_voltage                            |
| 10 |    overall_state, inverter_frequency, dry_contact1_status, grid_relay_status,    |
|    | load_l2_voltage, pv1_current, load_l1_voltage, dry_contact2_status, pv2_current, |
|    |         battery_1_bms_charging_voltage, battery_1_bms_hardware_version,          |
|    | undefined_load_relay_status, inv_relay_status, grid_l3_voltage, grid_connected,  |
|    |       battery_1_bms_max_discharge_current_limit, inverter_voltage, fault,        |
|    |  battery_1_bms_discharging_voltage, sd_status, battery_1_bms_software_version,   |
|    |    radiator_temperature, battery_1_bms_type, gen_l1_volts, battery_1_current,    |
|    |              battery_1_bms_discharging_current_limit, pv2_voltage,               |
|    |           grid_give_power_to_relay_status, battery_charge_efficiency,            |
|    | battery_1_bms_fault_flag, load_l3_voltage, battery_1_bms_soc, battery_1_bms_soh, |
|    |    pv1_voltage, battery_1_temperature, battery_1_bms_charging_current_limit,     |
|    |           battery_1_bms_current, generator_relay_status, gen_l3_volts,           |
|    |  battery_1_bms_rated_ah, grid_current, battery_1_bms_alarm_flag, gen_l2_volts,   |
|    |     battery_1_bms_temperature, dc_transformer_temperature, grid_l2_voltage,      |
|    |    grid_l1_voltage, grid_frequency, battery_1_bms_voltage, battery_1_voltage,    |
|    |              battery_1_soc, battery_1_bms_max_charge_current_limit               |
| 60 |         total_grid_import, total_pv_energy, day_load_energy, date_time,          |
|    |      day_active_energy, day_gen_energy, day_grid_export, total_grid_export,      |
|    |            day_grid_import, total_load_energy, total_battery_charge,             |
|    |           total_battery_discharge, day_battery_charge, day_pv_energy,            |
|    |                    day_battery_discharge, total_active_energy                    |
+----+----------------------------------------------------------------------------------+
11:04:29 INFO    Report every (inverter >1)
+-----+----------------------------------------------------------------------------------+
|  s  |                                     Sensors                                      |
+-----+----------------------------------------------------------------------------------+
|  10 |        grid_l3_power, grid_power, grid_l2_power, load_l3_power, pv_power,        |
|     |   b_phase_power_on_the_inner_side_of_the_grid, gen_l1_power, battery_1_power,    |
|     |      gen_l3_power, grid_side___inside_total_apparent_power, inverter_power,      |
|     |      load_l2_power, inverter_l1_power, pv2_power, load_l1_power, gen_power,      |
|     |                     pv1_power, grid_l1_power, grid_ct_power,                     |
|     |       total_active_power_from_side_to_side_of_the_grid, inverter_l3_power,       |
|     |            c_phase_power_on_the_inner_side_of_the_grid, gen_l2_power,            |
|     |    a_phase_power_on_the_inner_side_of_the_grid, load_power, inverter_l2_power    |
|  30 |     min_pv_power_for_gen_start, battery_1_bms_other_flag___battery_1_sleep,      |
|     |  generator_charge_start_battery_soc, battery_restart_capacity, grid_signal_on,   |
|     |          battery_float_voltage, configured_grid_phases, prog6_capacity,          |
|     |      grid_charge_start_battery_soc, battery_1_wake_up, prog_monday_enabled,      |
|     |        gen_signal_on, battery_equalization_hours, prog_wednesday_enabled,        |
|     |     export_limit_power, generator_ac_couple_frz_high, prog_saturday_enabled,     |
|     |   use_timer, prog3_time, prog1_charge, prog5_charge, parallel_battery_1_and_2,   |
|     |     prog_thursday_enabled, time_synchronization, prog3_voltage, prog2_power,     |
|     |         prog6_charge, prog5_voltage, drm, prog3_charge, prog2_capacity,          |
|     |              generator_cooling_time, battery_equalization_voltage,               |
|     |              grid_charge_battery_current, prog1_time, prog4_power,               |
|     |     battery_1_bms_other_flag___battery_1_force_charge, auto_dim, prog4_time,     |
|     |    prog5_capacity, prog_sunday_enabled, battery_low_voltage, prog4_capacity,     |
|     |  battery_restart_voltage, prog2_charge, prog3_power, system_zero_export_power,   |
|     |      prog2_voltage, max_solar_power, loss_of_lithium_battery_report_fault,       |
|     |       prog4_voltage, battery_capacity_current, battery_max_charge_current,       |
|     |   prog6_power, generator_port_usage, battery_shutdown_voltage, prog6_voltage,    |
|     |    battery_equalization_days, battery_resistance, configured_grid_frequency,     |
|     |     external_relay, battery_wake_up, prog6_time, battery_shutdown_capacity,      |
|     |    gen_peak_shaving, prog_friday_enabled, solar_export, prog_tuesday_enabled,    |
|     |     load_limit, generator_charge_battery_current, prog_time_of_use_enabled,      |
|     |            prog2_time, battery_max_discharge_current, prog1_capacity,            |
|     |   lithium_hv_bms_protocol, prog5_time, grid_peak_shaving, battery_type, am_pm,   |
|     | generator_off_soc, generator_on_soc, prog5_power, prog1_voltage, priority_load,  |
|     |          grid_peak_shaving_power, prog3_capacity, beep, grid_standard,           |
|     | battery_1_bms_other_flag___battery_2_force_charge, generator_max_operating_time, |
|     |      prog1_power, grid_charge_enabled, battery_low_capacity, prog4_charge,       |
|     |               generator_charge_enabled, battery_absorption_voltage               |
|  60 |       overall_state, grid_give_power_to_relay_status, dry_contact1_status,       |
|     |          grid_relay_status, battery_1_bms_fault_flag, date_time, fault,          |
|     |         dry_contact2_status, sd_status, battery_1_bms_software_version,          |
|     |   battery_1_bms_hardware_version, generator_relay_status, battery_1_bms_type,    |
|     |          undefined_load_relay_status, inv_relay_status, grid_connected,          |
|     |                             battery_1_bms_alarm_flag                             |
| 120 | inverter_frequency, load_l2_voltage, pv1_current, load_l1_voltage, pv2_current,  |
|     |       battery_1_bms_charging_voltage, total_load_energy, grid_l3_voltage,        |
|     |  battery_1_bms_max_charge_current_limit, total_active_energy, total_pv_energy,   |
|     |   battery_1_bms_max_discharge_current_limit, inverter_voltage, day_gen_energy,   |
|     |      battery_1_bms_discharging_voltage, total_grid_export, day_grid_import,      |
|     | radiator_temperature, total_battery_discharge, gen_l1_volts, battery_1_current,  |
|     |     battery_1_bms_discharging_current_limit, pv2_voltage, total_grid_import,     |
|     | battery_charge_efficiency, day_load_energy, load_l3_voltage, battery_1_bms_soc,  |
|     |              battery_1_bms_soh, pv1_voltage, battery_1_temperature,              |
|     |    battery_1_bms_charging_current_limit, battery_1_bms_current, gen_l3_volts,    |
|     | battery_1_bms_rated_ah, total_battery_charge, day_battery_charge, day_pv_energy, |
|     |              grid_current, gen_l2_volts, battery_1_bms_temperature,              |
|     | dc_transformer_temperature, grid_l2_voltage, day_active_energy, grid_l1_voltage, |
|     |    day_grid_export, grid_frequency, battery_1_bms_voltage, battery_1_voltage,    |
|     |                       battery_1_soc, day_battery_discharge                       |
| 300 |           grid_phase_warning, parallel_communication_quality_warning,            |
|     |  battery_1_manufacturer, device_type, fan_warning, lithium_battery_loss_warning  |
+-----+----------------------------------------------------------------------------------+

no errors!

image

Thanks!