CHANGE MODBUS ADDRESS POWER METER (ENTES - DELTA DPM530A) Download: [Untitled4_102_09112020.zip] (https://github.com/khomkrit01/service_center_delta_scada/files/5207037/Untitled4_102_09112020.zip)
Modbus RW Detail Current 0,3,16#4006,D2230,6 (Entes) 45,3,16#0120,DXXX,6 (DPM530A) V,Hz,PQS 0,3,16#402C,D2236,18 (Entes) 45,3,16#0108,DXXX,6 (DPM530A) Voltage 45,3,16#0142,DXXX,2 (DPM530A) Hz 45,3,16#0144,DXXX,2 (DPM530A) kW 45,3,16#014C,DXXX,2 (DPM530A) kVAR 45,3,16#0154,DXXX,2 (DPM530A) kVA Demand,kWh 0,3,16#4072,D2254,8 (Entes) 45,3,16#015C,DXXX,2 (DPM530A) kWh 45,3,16#0198,DXXX,2 (DPM530A) Demand PF 0,3,16#4092,D2262,2 (Entes) 45,3,16#0132,DXXX,2 (DPM530A) PF
Step 1: Add Function Block for Loop Read Data from DPM530A
Step 2: Change D Register for reports & graphic SCADA (*Please Check reference from original ladder) then change in "S" at "MODRW"
NOTE Now ladder ip.102 is Inactivate Network for disabled old ladder (Enter Meter) begin Network 25 to Network 28 but can check original D register number from that
MODBUS ADDRESS - DELTA DPM530A
Manual Download: DPM-C530A_UM_EN_20161018.pdf
Voltage
Current
kW
Demand
kVAR
kVA
Hz
PF
kWh (Delta Used)
Energy