Open khomkrit01 opened 4 years ago
PROBLEM 01 Re-check Formula - TR (kW/Ton) Chiller Trance Delta 5 PROBLEM=Formula Alert 'Get Result Failed'
Formula Name: DT5_trane_kw_tr Output: Var908 Detail: 'PM5053!P1!I/O 8' / '(System)!Vars!Var 907' Changed Detail to 'PM5053!Basic!kW Total' / '(System)!Vars!Var 907'**
Var 907 Is Output from formula name: DT5_trane_RT Detail: ('(System)!Vars!Var 901' *'FLOW DT5!P3!I/O 3') / 24+0.01
EDIT STATUS SUCCESS, 09/15/2020 10:19:00
SIM. TEST
DAServer Manager > Deafult Group > Local > ArchestrA.DASMBTCP.3 > Configuration > New_TCPIP_PORT000 Link Documents https://1drv.ms/x/s!Ag0FpZFBzz7xhMBSPHCqVcNDqGWZnQ?e=nuaKF9
PROBLEM 02 Difference Config. SMC between server ip33 and ip2
IP33
DELETE List
IP2
DELETE List
PROBLEM 03 Unit Report Chiller Climaveneta No.4 - Delta 5
Pressure New Chiller CONDENSER tag_col_014 P1 >> Psi to Bar (FLOW DT5!P5!I/O 3 >> Var 150 tag_col_015 P2 >> Psi to Bar (FLOW DT5!P5!I/O 4 >> Var 151 SUCCESS 20/09/2020 16:43:30
Pressure New Chiller COOLER tag_col_025 P3 >> Psi to Bar (FLOW DT5!P5!I/O 1 >> Var 152 tag_col_026 P4 >> Psi to Bar (FLOW DT5!P5!I/O 2 >> Var 153 SUCCESS 20/09/2020 16:43:30
COND P tag_col_019 P1-P2 (Var 708) 'FLOW DT5!P5!I/O 4' - 'FLOW DT5!P5!I/O 3' >> '(System)!Vars!Var 151' - '(System)!Vars!Var 150' SUCCESS 20/09/2020 16:53:01
COOL P tag_col_030 P3-P4 (Var 712) 'FLOW DT5!P5!I/O 2' - 'FLOW DT5!P5!I/O 1' >> '(System)!Vars!Var 153' - '(System)!Vars!Var 152' SUCCESS 20/09/2020 16:53:01
Formula Report Chiller Climaveneta No.4 - Delta 5
Mapping Tags
SUCCESS 19/09/2020 13:37:01
File Export System_20200920_170046.xlsx
LISTING REPORTS - DELTA5
Reference Delta 1 - Climaveneta
TMO6209162.PDF CN6306-10125_New Config Link Chiller Data_Rev2(BOQ).pdf CN6306-10125_New Config Link Chiller Data_Rev2(QUO).pdf