Closed minstrel1983 closed 3 days ago
Problem is clear now - parasitic inductance of wires.
Parallel winding in the primary inductive was bad idea.
New transformer desing coming soon.
Alternative solution - bring transfer as closest as possible to H-Bridge. Max distance - 5-10 cm.
The current transformer design is unsuitable. The current transformer ratio is definitely insufficient.
Why the current design is problematic:
New transformer design uploaded https://github.com/kinetikalab/project_aetheris/blob/main/power_electronics/transformer/README.md
To be tested next week in real conditions.
Transformer design updated https://github.com/kinetikalab/project_aetheris/blob/main/power_electronics/transformer/README.md
The problem was with parasitic capacity. Now it fixed. New transformer has very low parasitic capacity ~10 pF.
Tested in discharge - works perfect.
The current transformer design should ensure a coupling coefficient of approximately 0.8-0.9, but current measurements show only 0.5.
Hypothesis:
Stray inductance in the primary winding is likely due to a questionable design of the primary windings.
Outcomes: