Modbus connection problems #8

Closed littleyoda closed 3 months ago

littleyoda commented 4 months ago
          Morning, may be i have the same problem. If i make an reboot of the system (hoass), the network is confused. In the Logviewer i have this Message every 2 seconds: WARNING (Mainthread) (pymodbus.logging) Failed to connect. If i recover the backup made before restart everything is fine.

Originally posted by @ulrich379 in https://github.com/littleyoda/ha-pysmaplus/issues/4#issuecomment-2216707778

littleyoda commented 4 months ago

I assume you are using the SHM2 with Grid Guard Code.

  1. Please enable the debug logging

grafik

  1. Try to reload the integration

grafik

  1. Can you please test if you are able to connect to your inverter using a modbus program? e.g. https://qmodbus.sourceforge.net/ Please you there config as shown in the screenshot. But change the IP-Address. grafik
ulrich379 commented 4 months ago

I have a working Modbus Connection to the invererter: modbus  - name: sma_hub     type: tcp     host: 10.10.10.173     port: 502     sensors: !include sma_adresses.yaml     delay: 0     message_wait_milliseconds: 30     timeout: 5 I have testet with deaktivatet modbus.yaml but the error persist.

littleyoda commented 4 months ago

You wrote:

Sorry, vor late answer. I have an X20 and an EMeter20, no SHM2.

I have just lost the overview.

Which interface are you using?

grafik

If you are not using "Sunny Home Manager 2 with Grid Guard Code", your problem has nothing to do with my integration.

The Energy Meter 2 does not support modbus, as far as I know.

We can also continue in german, if it is easier for you.

ulrich379 commented 4 months ago

I use the ennexos interface