House Consumption is wrong on low load #191

Closed smileyman-1 closed 11 months ago

smileyman-1 commented 1 year ago

If consumption is low and there is no pv-input (at night), the House Consumption value is incorrect.

image

At night, a generation of 15 watts is detected in this way.

On-grid Export Power shows the same wrong value. (In PV-Master the value is correct.) On-grid Power and Plant Power, on the other hand, usually - but not always - shows at this time the correct value. (But this values are always positiv and do not switch to minus for importing)

image

When the load is higher House Consumption shows the correct values.

image image

Inverter: GW3068-EM

Paja-git commented 1 year ago

The house consumption is a calculated value. PV1Power+PV2Power+BaterryPower-ActivePower. ModBus registers are read sequentially, the inverter's probes have some precision also. So, small calc errors can happen.