Add Form Factor to power outlet/port #792

Closed elmmare closed 4 years ago

elmmare commented 7 years ago

I'm tracing the power connection between: devices - rack PDUs rack PDUs - Power Panels using Power Outlet and Power Port items.

A better description of the real world should include a "Form Factor" field describing the port/outlet connector. (as we have on interface "Form Factor")

Some of the values are: IEC60320 (usually found on device and pdu outlet) C13 C14 C19 C20

IEC60309 (usually found in PDU inlet ) 32A (2P+E) 32A (3P+N+E) NEMA ...

Adding a an "icon" field can further help (http://www.internationalconfig.com/): c-20 c-19 iec-60309-20-16amp230-400volt 1 iec-60309-30-32amp230-400volt 1 iec-60309-20-15amp250volt 1 iec-60309-30-32amp230volt 1

jeremystretch commented 7 years ago

This is something I've had on the back burner for a while, but there's a lot more that needs to be added along with this (circuit amperage, voltage, phase, etc.), so I'm going to mark it as a major feature.

rc5hack commented 7 years ago

adding also an optional "color" option for each outlet sounds like a good addition here (some PDU could have different colors outlets of the same type, e.g. black outlet is normal, and red outlet is UPS-backuped)

jsenecal commented 7 years ago

We also got rack PDUs with a color per phase. black-gray-white

On Mon, Feb 6, 2017, 03:14 Antonio Kless, notifications@github.com wrote:

adding also an optional "color" option for each outlet sounds like a good addition here (some PDU could have different colors outlets of the same type, e.g. black outlet is normal, and red outlet is UPS-backuped)

— You are receiving this because you are subscribed to this thread. Reply to this email directly, view it on GitHub https://github.com/digitalocean/netbox/issues/792#issuecomment-277611167, or mute the thread https://github.com/notifications/unsubscribe-auth/ABfg5hwVGabC4w5NID4oOxJl4AmEgWf1ks5rZtaAgaJpZM4LhorG .

bmsmithvb commented 7 years ago

Is it possible to obtain 0U rack PDUs?

jeremystretch commented 7 years ago

@bmsmithvb Yes, very easily. Just set the device type's height to 0U.

puck commented 7 years ago

If colours per phase are implemented, then they'll need to be customisable. We use different colours in NZ.

jasonguy commented 6 years ago

It is common practice in many DCs to mount the long PDUs (like a 24-port APC), vertically on the back of a rack. I set it as an unracked device currently, however it would be cool to add something to the graphical rack view, showing the vertically mounted PDU. This could also simply be displayed on the PDU detail page, along with information from the smart PDU.

wrouesnel commented 6 years ago

Technically then you'd like to also mark a vertical PDU by what side of the housing its on (important if you were trying to tell someone which phase to unplug / replug).

fischa commented 5 years ago

We use PDUs that have all or some switchable power outlets. Would be nice to have that as Boolean or yes/no field available (per power outlet) too.

falz commented 5 years ago

Also give consideration to DC power. We recently begun testing Netbox and added some DC fuse panels as power connections.

Here are a few examples of DC panels that we, and likely others use. Between these two, there are 3 different fuse types. There are certainly many others as well:

http://www.trimminc.com/download/8271001001.pdf - 4x4 TPA + 5x5 GMT http://www.trimminc.com/download/7272101001.pdf - 8x8 TPM

.. each fuse type can have different amperage (1, 3, 5, 10... etc). In our case everything worked just fine as-is, we labeled the power outlets as "TPA A[1-4] and "TPA B[1-4]".

The only important piece we were unable to document was fuse size (amps) and DC voltage (-48v). Voltage, at least in our case, is always static as we've standardized on -48v DC.

DocCox commented 5 years ago

My team primarily works in DC environments - and power mapping is what keeps us considering different DCIM tools. We ended up with a home rolled flask solution but there's just not enough time to maintain it so Netbox is up for consideration

For DC power on the internal tool we used the following Cable gauge Cable color (helpful - different standards are everywhere) Cable length Cable battery/return A/Z side terminations (Lug type/length/spacing/holes)

Fuse panels typically support 1 or more type of fuses/breakers now. Fuses had Amperage Form factor Losses

Panels themselves had Inputs/outputs with the above A/Z termination points Internal Busses

The buses had Compatible form factor(s) Qty of connectors Maximum amperage (By bus and form factor) (Ex: In those 4x5 TPA/GMT panels its not uncommon to see 100-200A rating for the TPA bus and a 60A rating on the GMT bus. I see guys loading 60A GMT buses to 80A+ pretty frequently, or throwing 20A GMT fuses in a bus rated for 15A fuses.)

Just glancing over the version of netbox I have locally everything looks pretty close to whats needed Fuse panels could be treated as chassis, busses would more or less be cards/modules, and the power runs over the existing port setup. Power could calculate fairly accurately from the top most device in the chain with this sort of setup - in some of our locations we own the whole shebang and in other vendors are providing us power to our BDFBs/inverters or straight to fuse panels

bluikko commented 5 years ago

I would like to add my 2 cents in this feature request: if 0U vertical devices (my use case is large PDUs) are somehow rendered in rack views, please allow at least 3 of them horizontally and/or on the "depth axis".

jeremystretch commented 4 years ago

Adding this as reference material: https://twitter.com/network_phil/status/1181563103034724352

Also this excellent cheat sheet: http://blog.packetsar.com/wp-content/uploads/Power_and_Cooling_Cheat_Sheet.pdf

pyro3d commented 4 years ago

+1 for more DC support. Have a number of devices off rectifiers+battery strings or off a PDU in a CO where it's needed. Copper grounding bars would also be nice.

jeremystretch commented 4 years ago

I'm having a difficult time determining what to include for the plug/outlet types. It seems there are several series of standards:

Does it make sense to include the ITA types (A through O) as their own types, even though they technically overlap with other standards? (For example, type A is the same as NEMA 1-15.) If not, we could just list individual country-specific types as their own series.

swerveshot commented 4 years ago

Hi @jeremystretch! For your information; in the Netherlands we mostly encounter IEC 60320 (C13/14 and C19/C20) in the datacenter. And occasionally a CEE 7 'shuko' type plug.

jeremystretch commented 4 years ago

This work is mostly done, but leaving the issue open for additional feedback regarding specific types.

bluikko commented 4 years ago

Can you confirm that "universal" outlet sockets are supported?

I have to admit that we have a few rack-mount "PDU"s with these for random power bricks. Here is an example of how the sockets look: https://www.havells.com/content/dam/havells/consumer/switches/Fabio-modular-range/sockets/AHFKUXW133/cover.png

ThomasADavis commented 4 years ago

Ok, just found this..

1) We have racks that have hardwired connections in them - so please add 'hardwired'.

2) We have systems coming in that will have 150A power feeds. The current feed max is about ~100A - I get:

<class 'django.db.utils.DataError'>

smallint out of range

Getting into the 1200A or better range for feeds can mean I create feeds from the substations all the way to rack. In case your wondering what the high current is used for, it's what a supercomputer cabinet pulls. :)

thanks! thomas

brotherdust commented 4 years ago

I have many devices that use coaxial power connectors. Would it make sense to add these standards as well? https://en.wikipedia.org/wiki/Coaxial_power_connector

In my use case, the coaxial connectors are feeding from a power brick (usually C14) or they are spliced into a DC power bus. Would it also make sense to have a way to track if the device uses a power brick and the specifications of said power brick?

bluikko commented 4 years ago

I thought "barrel connector" is in more wide-spread usage than coaxial power connector. Anyone know which one is more usual?

I'd also still want to see the "multi-standard"/"international" customer/domestic connector... or at least "Other" type.

brotherdust commented 4 years ago

Barrel connector is de-facto usage, as you suggest. Coaxial is what’s used in the standard. Either way, same thing. Just didn’t want to confuse matters when I was making reference to Wikipedia article and it’s called coaxial there. 😁