#803 Single phase Regulators cannot converge with control modes in NR, #1530

Open nikhilgupta10 opened 8 years ago

nikhilgupta10 commented 8 years ago

An issue was reported where the iteration limit was reached on a single-phase regulator performing output_voltage control. I confirmed this behavior was happening for NR only with control modes output_voltage, line drop compensation, and remote node. I will attach the file I used to confirm this behavior. Please not that this behavior is only happening in NR. Also, regardless of the solver used, maximum tap reached warnings show up for the phases not present on the regulator. Checking the code I saw that there are no phase checks for triggering tap changes for the previously mentioned control modes.

,

nikhilgupta10 commented 8 years ago

nikhilgupta10 imported these comments from Sourceforge: The user dchassin does not exist anymore. Therefore assigning this to afisher1.

, Similar issue in ully tapped and no time delay\ regulators causing convergence failures (iteration limit reached). I contend this is bad model files and/or user error, but how regulators iterate a ailed\ positions may need to be re-evaluated.

Side note: Kevin Schneider has a bunch of files that fail these regulator scenarios in a variety of methods.

,

Diff: