nutdotnet / WinNUT-Client

WinForms-based client for monitoring your Uninterruptible Power Supply (UPS) connected to a Network UPS Tools (NUT) server.
GNU General Public License v3.0
209 stars 19 forks source link

0 W load #122

Open Jefronty opened 10 months ago

Jefronty commented 10 months ago

My UPS is on a Synology NAS, I added my IP to permitted devices and am able to connect, but the load wattage graph always shows 0, all others seem to be working normally. Even after adjusting the settings for North American grid Voltage and frequency I'm getting 0% and 0 W on UPS load. My UPS is APC and I installed WinNUT on Windows 11 Pro.

gbakeman commented 10 months ago

This is likely related to #120 . The Load display is showing 0 most likely because WinNUT could not detect a supported method for calculating the load from your UPS. Please attach the latest log with a session of you connecting to your UPS, and also please upload the output from the variables list (in the Files menu.)

Thank you!

gbakeman commented 9 months ago

Hi @Jefronty, we've had a Pre-Release of WinNUT since we last interacted, and I wanted to see if you're still experiencing this issue. Please let me know when you can.

Chainfire commented 6 months ago

FINAL EDIT: I am an absolute pancake. Everything is working fine. Apparently this UPS simply doesn't register loads below 5% of capacity. Everything seems to work with a bigger load applied.

-- original post --

@gbakeman I have the same issue, APC Back-UPS BX2200MI (Nov 23) connected through a Synology (DSM 6.2) NAS.

I would like to note that this is a replacement UPS, I was previously using a few years older version of the APC Back-UPS BX750MI (mid-19) which battery just died, prompting this replacement. WinNUT 2.0 was working perfectly with that UPS on this same unit. Just trying to clarify nothing in the setup changed aside from switching out the UPS, and it used to work.

I have the 0%/0W load issue, immediately since connecting the new NAS. I just updated WinNUT to Pre-Release v2.3.8834, the problem persists.

I feel the battery voltage may be wrong as well, shouldn't it be 12V ? I honestly don't know. Additionally, it has been stuck on 97% charge, which could be UPS self-protection or a wrong reading, by now it should be fully charged. EDIT: both these things are a non-issue, voltage is correct, so is charge %

UPS variables
ups (American Power Conversion/Back-UPS BX2200MI/Unknown)
battery.charge (Description unavailable) : 97
battery.charge.low (Description unavailable) : 10
battery.mfr.date (Description unavailable) : 2001/01/01
battery.runtime (Description unavailable) : 3701
battery.runtime.low (Description unavailable) : 120
battery.type (Description unavailable) : PbAc
battery.voltage (Description unavailable) : 28.4
battery.voltage.nominal (Description unavailable) : 24.0
device.mfr (Description unavailable) : American Power Conversion
device.model (Description unavailable) : Back-UPS BX2200MI
device.serial (Description unavailable) : 9B2342A06751
device.type (Description unavailable) : ups
driver.name (Description unavailable) : usbhid-ups
driver.parameter.pollfreq (Description unavailable) : 30
driver.parameter.pollinterval (Description unavailable) : 5
driver.parameter.port (Description unavailable) : auto
driver.version (Description unavailable) : DSM6-2-25510-201118
driver.version.data (Description unavailable) : APC HID 0.95
driver.version.internal (Description unavailable) : 0.38
input.sensitivity (Description unavailable) : medium
input.transfer.high (Description unavailable) : 295
input.transfer.low (Description unavailable) : 145
input.voltage (Description unavailable) : 232.0
input.voltage.nominal (Description unavailable) : 230
ups.beeper.status (Description unavailable) : disabled
ups.delay.shutdown (Description unavailable) : 20
ups.load (Description unavailable) : 0
ups.mfr (Description unavailable) : American Power Conversion
ups.mfr.date (Description unavailable) : 2023/10/19
ups.model (Description unavailable) : Back-UPS BX2200MI
ups.productid (Description unavailable) : 0002
ups.realpower.nominal (Description unavailable) : 1200
ups.serial (Description unavailable) : 9B2342A06751
ups.status (Description unavailable) : OL CHRG
ups.test.result (Description unavailable) : Done and passed
ups.timer.reboot (Description unavailable) : 0
ups.timer.shutdown (Description unavailable) : -1
ups.vendorid (Description unavailable) : 051d
Log (long)
13/03/2024 14:24:35 [57840, Logger]: WinNUT Client 2.3.8834.24333 Log file init
==== History of 200 previous events ====
[1] 13/03/2024 14:24:23 [57840, UPS_Device]: Apply Fallback Value when retrieving output.frequency
[2] 13/03/2024 14:24:23 [57840, UPS_Device]: input.frequency is not supported by server.
[3] 13/03/2024 14:24:23 [57840, UPS_Device]: Apply Fallback Value when retrieving input.frequency
[4] 13/03/2024 14:24:23 [57840, UPS_Device]: output.voltage is not supported by server.
[5] 13/03/2024 14:24:23 [57840, UPS_Device]: Apply Fallback Value when retrieving output.voltage
[6] 13/03/2024 14:24:23 [57840, UPS_Device]: UPS statuses have not changed since last update, skipping.
[7] 13/03/2024 14:24:23 [57840, WinNUT]: Updating UPS data for Form.
[8] 13/03/2024 14:24:23 [57840, WinNUT]: Updating battery icons based on charge percent: 97%
[9] 13/03/2024 14:24:23 [57840, WinNUT]: Calculated estimated remaining battery time: 01:01:41
[10] 13/03/2024 14:24:23 [57840, WinNUT]: Update Dial
[11] 13/03/2024 14:24:23 [57840, WinNUT]: Update Icon
[12] 13/03/2024 14:24:23 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
On Line
Battery OK
[13] 13/03/2024 14:24:23 [57840, WinNUT]: Battery Status => Discharging
[14] 13/03/2024 14:24:24 [57840, UPS_Device]: Enter Retrieve_UPS_Datas
[15] 13/03/2024 14:24:24 [57840, UPS_Device]: output.frequency is not supported by server.
[16] 13/03/2024 14:24:24 [57840, UPS_Device]: Apply Fallback Value when retrieving output.frequency
[17] 13/03/2024 14:24:24 [57840, UPS_Device]: input.frequency is not supported by server.
[18] 13/03/2024 14:24:24 [57840, UPS_Device]: Apply Fallback Value when retrieving input.frequency
[19] 13/03/2024 14:24:24 [57840, UPS_Device]: output.voltage is not supported by server.
[20] 13/03/2024 14:24:24 [57840, UPS_Device]: Apply Fallback Value when retrieving output.voltage
[21] 13/03/2024 14:24:24 [57840, UPS_Device]: UPS statuses have not changed since last update, skipping.
[22] 13/03/2024 14:24:24 [57840, WinNUT]: Updating UPS data for Form.
[23] 13/03/2024 14:24:24 [57840, WinNUT]: Updating battery icons based on charge percent: 97%
[24] 13/03/2024 14:24:24 [57840, WinNUT]: Calculated estimated remaining battery time: 01:01:41
[25] 13/03/2024 14:24:24 [57840, WinNUT]: Update Dial
[26] 13/03/2024 14:24:24 [57840, WinNUT]: Update Icon
[27] 13/03/2024 14:24:24 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
On Line
Battery OK
[28] 13/03/2024 14:24:24 [57840, WinNUT]: Battery Status => Discharging
[29] 13/03/2024 14:24:25 [57840, UPS_Device]: Enter Retrieve_UPS_Datas
[30] 13/03/2024 14:24:25 [57840, UPS_Device]: output.frequency is not supported by server.
[31] 13/03/2024 14:24:25 [57840, UPS_Device]: Apply Fallback Value when retrieving output.frequency
[32] 13/03/2024 14:24:25 [57840, UPS_Device]: input.frequency is not supported by server.
[33] 13/03/2024 14:24:25 [57840, UPS_Device]: Apply Fallback Value when retrieving input.frequency
[34] 13/03/2024 14:24:25 [57840, UPS_Device]: output.voltage is not supported by server.
[35] 13/03/2024 14:24:25 [57840, UPS_Device]: Apply Fallback Value when retrieving output.voltage
[36] 13/03/2024 14:24:25 [57840, UPS_Device]: UPS statuses have not changed since last update, skipping.
[37] 13/03/2024 14:24:25 [57840, WinNUT]: Updating UPS data for Form.
[38] 13/03/2024 14:24:25 [57840, WinNUT]: Updating battery icons based on charge percent: 97%
[39] 13/03/2024 14:24:25 [57840, WinNUT]: Calculated estimated remaining battery time: 01:01:41
[40] 13/03/2024 14:24:25 [57840, WinNUT]: Update Dial
[41] 13/03/2024 14:24:25 [57840, WinNUT]: Update Icon
[42] 13/03/2024 14:24:25 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
On Line
Battery OK
[43] 13/03/2024 14:24:25 [57840, WinNUT]: Battery Status => Discharging
[44] 13/03/2024 14:24:26 [57840, UPS_Device]: Enter Retrieve_UPS_Datas
[45] 13/03/2024 14:24:26 [57840, UPS_Device]: output.frequency is not supported by server.
[46] 13/03/2024 14:24:26 [57840, UPS_Device]: Apply Fallback Value when retrieving output.frequency
[47] 13/03/2024 14:24:26 [57840, UPS_Device]: input.frequency is not supported by server.
[48] 13/03/2024 14:24:26 [57840, UPS_Device]: Apply Fallback Value when retrieving input.frequency
[49] 13/03/2024 14:24:26 [57840, UPS_Device]: output.voltage is not supported by server.
[50] 13/03/2024 14:24:26 [57840, UPS_Device]: Apply Fallback Value when retrieving output.voltage
[51] 13/03/2024 14:24:26 [57840, UPS_Device]: UPS statuses have not changed since last update, skipping.
[52] 13/03/2024 14:24:26 [57840, WinNUT]: Updating UPS data for Form.
[53] 13/03/2024 14:24:26 [57840, WinNUT]: Updating battery icons based on charge percent: 97%
[54] 13/03/2024 14:24:26 [57840, WinNUT]: Calculated estimated remaining battery time: 01:01:41
[55] 13/03/2024 14:24:26 [57840, WinNUT]: Update Dial
[56] 13/03/2024 14:24:26 [57840, WinNUT]: Update Icon
[57] 13/03/2024 14:24:26 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
On Line
Battery OK
[58] 13/03/2024 14:24:26 [57840, WinNUT]: Battery Status => Discharging
[59] 13/03/2024 14:24:27 [57840, UPS_Device]: Enter Retrieve_UPS_Datas
[60] 13/03/2024 14:24:27 [57840, UPS_Device]: output.frequency is not supported by server.
[61] 13/03/2024 14:24:27 [57840, UPS_Device]: Apply Fallback Value when retrieving output.frequency
[62] 13/03/2024 14:24:27 [57840, UPS_Device]: input.frequency is not supported by server.
[63] 13/03/2024 14:24:27 [57840, UPS_Device]: Apply Fallback Value when retrieving input.frequency
[64] 13/03/2024 14:24:27 [57840, UPS_Device]: output.voltage is not supported by server.
[65] 13/03/2024 14:24:27 [57840, UPS_Device]: Apply Fallback Value when retrieving output.voltage
[66] 13/03/2024 14:24:27 [57840, UPS_Device]: UPS statuses have not changed since last update, skipping.
[67] 13/03/2024 14:24:27 [57840, WinNUT]: Updating UPS data for Form.
[68] 13/03/2024 14:24:27 [57840, WinNUT]: Updating battery icons based on charge percent: 97%
[69] 13/03/2024 14:24:27 [57840, WinNUT]: Calculated estimated remaining battery time: 01:01:41
[70] 13/03/2024 14:24:27 [57840, WinNUT]: Update Dial
[71] 13/03/2024 14:24:27 [57840, WinNUT]: Update Icon
[72] 13/03/2024 14:24:27 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
On Line
Battery OK
[73] 13/03/2024 14:24:27 [57840, WinNUT]: Battery Status => Discharging
[74] 13/03/2024 14:24:28 [57840, UPS_Device]: Enter Retrieve_UPS_Datas
[75] 13/03/2024 14:24:28 [57840, UPS_Device]: output.frequency is not supported by server.
[76] 13/03/2024 14:24:28 [57840, UPS_Device]: Apply Fallback Value when retrieving output.frequency
[77] 13/03/2024 14:24:28 [57840, UPS_Device]: input.frequency is not supported by server.
[78] 13/03/2024 14:24:28 [57840, UPS_Device]: Apply Fallback Value when retrieving input.frequency
[79] 13/03/2024 14:24:28 [57840, UPS_Device]: output.voltage is not supported by server.
[80] 13/03/2024 14:24:28 [57840, UPS_Device]: Apply Fallback Value when retrieving output.voltage
[81] 13/03/2024 14:24:28 [57840, UPS_Device]: UPS statuses have not changed since last update, skipping.
[82] 13/03/2024 14:24:28 [57840, WinNUT]: Updating UPS data for Form.
[83] 13/03/2024 14:24:28 [57840, WinNUT]: Updating battery icons based on charge percent: 97%
[84] 13/03/2024 14:24:28 [57840, WinNUT]: Calculated estimated remaining battery time: 01:01:41
[85] 13/03/2024 14:24:28 [57840, WinNUT]: Update Dial
[86] 13/03/2024 14:24:28 [57840, WinNUT]: Update Icon
[87] 13/03/2024 14:24:28 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
On Line
Battery OK
[88] 13/03/2024 14:24:28 [57840, WinNUT]: Battery Status => Discharging
[89] 13/03/2024 14:24:29 [57840, UPS_Device]: Enter Retrieve_UPS_Datas
[90] 13/03/2024 14:24:29 [57840, UPS_Device]: output.frequency is not supported by server.
[91] 13/03/2024 14:24:29 [57840, UPS_Device]: Apply Fallback Value when retrieving output.frequency
[92] 13/03/2024 14:24:29 [57840, UPS_Device]: input.frequency is not supported by server.
[93] 13/03/2024 14:24:29 [57840, UPS_Device]: Apply Fallback Value when retrieving input.frequency
[94] 13/03/2024 14:24:29 [57840, UPS_Device]: output.voltage is not supported by server.
[95] 13/03/2024 14:24:29 [57840, UPS_Device]: Apply Fallback Value when retrieving output.voltage
[96] 13/03/2024 14:24:29 [57840, UPS_Device]: UPS statuses have not changed since last update, skipping.
[97] 13/03/2024 14:24:29 [57840, WinNUT]: Updating UPS data for Form.
[98] 13/03/2024 14:24:29 [57840, WinNUT]: Updating battery icons based on charge percent: 97%
[99] 13/03/2024 14:24:29 [57840, WinNUT]: Calculated estimated remaining battery time: 01:01:41
[100] 13/03/2024 14:24:29 [57840, WinNUT]: Update Dial
[101] 13/03/2024 14:24:29 [57840, WinNUT]: Update Icon
[102] 13/03/2024 14:24:29 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
On Line
Battery OK
[103] 13/03/2024 14:24:29 [57840, WinNUT]: Battery Status => Discharging
[104] 13/03/2024 14:24:30 [57840, UPS_Device]: Enter Retrieve_UPS_Datas
[105] 13/03/2024 14:24:30 [57840, UPS_Device]: output.frequency is not supported by server.
[106] 13/03/2024 14:24:30 [57840, UPS_Device]: Apply Fallback Value when retrieving output.frequency
[107] 13/03/2024 14:24:30 [57840, UPS_Device]: input.frequency is not supported by server.
[108] 13/03/2024 14:24:30 [57840, UPS_Device]: Apply Fallback Value when retrieving input.frequency
[109] 13/03/2024 14:24:30 [57840, UPS_Device]: output.voltage is not supported by server.
[110] 13/03/2024 14:24:30 [57840, UPS_Device]: Apply Fallback Value when retrieving output.voltage
[111] 13/03/2024 14:24:30 [57840, UPS_Device]: UPS statuses have not changed since last update, skipping.
[112] 13/03/2024 14:24:30 [57840, WinNUT]: Updating UPS data for Form.
[113] 13/03/2024 14:24:30 [57840, WinNUT]: Updating battery icons based on charge percent: 97%
[114] 13/03/2024 14:24:30 [57840, WinNUT]: Calculated estimated remaining battery time: 01:01:41
[115] 13/03/2024 14:24:30 [57840, WinNUT]: Update Dial
[116] 13/03/2024 14:24:30 [57840, WinNUT]: Update Icon
[117] 13/03/2024 14:24:30 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
On Line
Battery OK
[118] 13/03/2024 14:24:30 [57840, WinNUT]: Battery Status => Discharging
[119] 13/03/2024 14:24:31 [57840, UPS_Device]: Enter Retrieve_UPS_Datas
[120] 13/03/2024 14:24:31 [57840, UPS_Device]: output.frequency is not supported by server.
[121] 13/03/2024 14:24:31 [57840, UPS_Device]: Apply Fallback Value when retrieving output.frequency
[122] 13/03/2024 14:24:31 [57840, UPS_Device]: input.frequency is not supported by server.
[123] 13/03/2024 14:24:31 [57840, UPS_Device]: Apply Fallback Value when retrieving input.frequency
[124] 13/03/2024 14:24:31 [57840, UPS_Device]: output.voltage is not supported by server.
[125] 13/03/2024 14:24:31 [57840, UPS_Device]: Apply Fallback Value when retrieving output.voltage
[126] 13/03/2024 14:24:31 [57840, UPS_Device]: UPS statuses have not changed since last update, skipping.
[127] 13/03/2024 14:24:31 [57840, WinNUT]: Updating UPS data for Form.
[128] 13/03/2024 14:24:31 [57840, WinNUT]: Updating battery icons based on charge percent: 97%
[129] 13/03/2024 14:24:31 [57840, WinNUT]: Calculated estimated remaining battery time: 01:01:41
[130] 13/03/2024 14:24:31 [57840, WinNUT]: Update Dial
[131] 13/03/2024 14:24:31 [57840, WinNUT]: Update Icon
[132] 13/03/2024 14:24:31 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
On Line
Battery OK
[133] 13/03/2024 14:24:31 [57840, WinNUT]: Battery Status => Discharging
[134] 13/03/2024 14:24:32 [57840, UPS_Device]: Enter Retrieve_UPS_Datas
[135] 13/03/2024 14:24:32 [57840, UPS_Device]: output.frequency is not supported by server.
[136] 13/03/2024 14:24:32 [57840, UPS_Device]: Apply Fallback Value when retrieving output.frequency
[137] 13/03/2024 14:24:32 [57840, UPS_Device]: input.frequency is not supported by server.
[138] 13/03/2024 14:24:32 [57840, UPS_Device]: Apply Fallback Value when retrieving input.frequency
[139] 13/03/2024 14:24:32 [57840, UPS_Device]: output.voltage is not supported by server.
[140] 13/03/2024 14:24:32 [57840, UPS_Device]: Apply Fallback Value when retrieving output.voltage
[141] 13/03/2024 14:24:32 [57840, UPS_Device]: UPS statuses have not changed since last update, skipping.
[142] 13/03/2024 14:24:32 [57840, WinNUT]: Updating UPS data for Form.
[143] 13/03/2024 14:24:32 [57840, WinNUT]: Updating battery icons based on charge percent: 97%
[144] 13/03/2024 14:24:32 [57840, WinNUT]: Calculated estimated remaining battery time: 01:01:41
[145] 13/03/2024 14:24:32 [57840, WinNUT]: Update Dial
[146] 13/03/2024 14:24:32 [57840, WinNUT]: Update Icon
[147] 13/03/2024 14:24:32 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
On Line
Battery OK
[148] 13/03/2024 14:24:32 [57840, WinNUT]: Battery Status => Discharging
[149] 13/03/2024 14:24:33 [57840, UPS_Device]: Enter Retrieve_UPS_Datas
[150] 13/03/2024 14:24:33 [57840, UPS_Device]: output.frequency is not supported by server.
[151] 13/03/2024 14:24:33 [57840, UPS_Device]: Apply Fallback Value when retrieving output.frequency
[152] 13/03/2024 14:24:33 [57840, UPS_Device]: input.frequency is not supported by server.
[153] 13/03/2024 14:24:33 [57840, UPS_Device]: Apply Fallback Value when retrieving input.frequency
[154] 13/03/2024 14:24:33 [57840, UPS_Device]: output.voltage is not supported by server.
[155] 13/03/2024 14:24:33 [57840, UPS_Device]: Apply Fallback Value when retrieving output.voltage
[156] 13/03/2024 14:24:33 [57840, UPS_Device]: UPS statuses have not changed since last update, skipping.
[157] 13/03/2024 14:24:33 [57840, WinNUT]: Updating UPS data for Form.
[158] 13/03/2024 14:24:33 [57840, WinNUT]: Updating battery icons based on charge percent: 97%
[159] 13/03/2024 14:24:33 [57840, WinNUT]: Calculated estimated remaining battery time: 01:01:41
[160] 13/03/2024 14:24:33 [57840, WinNUT]: Update Dial
[161] 13/03/2024 14:24:33 [57840, WinNUT]: Update Icon
[162] 13/03/2024 14:24:33 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
On Line
Battery OK
[163] 13/03/2024 14:24:33 [57840, WinNUT]: Battery Status => Discharging
[164] 13/03/2024 14:24:34 [57840, UPS_Device]: Enter Retrieve_UPS_Datas
[165] 13/03/2024 14:24:34 [57840, UPS_Device]: output.frequency is not supported by server.
[166] 13/03/2024 14:24:34 [57840, UPS_Device]: Apply Fallback Value when retrieving output.frequency
[167] 13/03/2024 14:24:34 [57840, UPS_Device]: input.frequency is not supported by server.
[168] 13/03/2024 14:24:34 [57840, UPS_Device]: Apply Fallback Value when retrieving input.frequency
[169] 13/03/2024 14:24:34 [57840, UPS_Device]: output.voltage is not supported by server.
[170] 13/03/2024 14:24:34 [57840, UPS_Device]: Apply Fallback Value when retrieving output.voltage
[171] 13/03/2024 14:24:34 [57840, UPS_Device]: UPS statuses have not changed since last update, skipping.
[172] 13/03/2024 14:24:34 [57840, WinNUT]: Updating UPS data for Form.
[173] 13/03/2024 14:24:34 [57840, WinNUT]: Updating battery icons based on charge percent: 97%
[174] 13/03/2024 14:24:34 [57840, WinNUT]: Calculated estimated remaining battery time: 01:01:41
[175] 13/03/2024 14:24:34 [57840, WinNUT]: Update Dial
[176] 13/03/2024 14:24:34 [57840, WinNUT]: Update Icon
[177] 13/03/2024 14:24:34 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
On Line
Battery OK
[178] 13/03/2024 14:24:34 [57840, WinNUT]: Battery Status => Discharging
[179] 13/03/2024 14:24:34 [57840, Pref_Gui]: Setting LogControl statuses.
[180] 13/03/2024 14:24:35 [57840, UPS_Device]: Enter Retrieve_UPS_Datas
[181] 13/03/2024 14:24:35 [57840, UPS_Device]: output.frequency is not supported by server.
[182] 13/03/2024 14:24:35 [57840, UPS_Device]: Apply Fallback Value when retrieving output.frequency
[183] 13/03/2024 14:24:35 [57840, UPS_Device]: input.frequency is not supported by server.
[184] 13/03/2024 14:24:35 [57840, UPS_Device]: Apply Fallback Value when retrieving input.frequency
[185] 13/03/2024 14:24:35 [57840, UPS_Device]: output.voltage is not supported by server.
[186] 13/03/2024 14:24:35 [57840, UPS_Device]: Apply Fallback Value when retrieving output.voltage
[187] 13/03/2024 14:24:35 [57840, UPS_Device]: UPS statuses have not changed since last update, skipping.
[188] 13/03/2024 14:24:35 [57840, WinNUT]: Updating UPS data for Form.
[189] 13/03/2024 14:24:35 [57840, WinNUT]: Updating battery icons based on charge percent: 97%
[190] 13/03/2024 14:24:35 [57840, WinNUT]: Calculated estimated remaining battery time: 01:01:41
[191] 13/03/2024 14:24:35 [57840, WinNUT]: Update Dial
[192] 13/03/2024 14:24:35 [57840, WinNUT]: Update Icon
[193] 13/03/2024 14:24:35 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
On Line
Battery OK
[194] 13/03/2024 14:24:35 [57840, WinNUT]: Battery Status => Discharging
[195] 13/03/2024 14:24:35 [57840, Pref_Gui]: Save Parameters.
[196] 13/03/2024 14:24:35 [57840, Pref_Gui]: WinNUT Added to Startup.
[197] 13/03/2024 14:24:35 [57840, Pref_Gui]: Pref_Gui Params Saved
[198] 13/03/2024 14:24:35 [57840, Pref_Gui]: Setting LogControl statuses.
[199] 13/03/2024 14:24:35 [57840, WinNUT]: Beginning WinNUT_PrefsChanged subroutine.
[200] 13/03/2024 14:24:35 [57840, Logger]: WinNUT Client 2.3.8834.24333 Log file init
==== Begin Live Log ====
13/03/2024 14:24:36 [57840, WinNUT]: Connection parameters Changed. Force Reconnect
13/03/2024 14:24:36 [57840, WinNUT]: Running Client disconnect subroutine.
13/03/2024 14:24:36 [57840, UPS_Device]: Processing request to disconnect...
13/03/2024 14:24:36 [57840, WinNUT]: Update all informations displayed to empty values
13/03/2024 14:24:36 [57840, WinNUT]: Update Icon
13/03/2024 14:24:36 [57840, WinNUT]: Status Icon Changed
13/03/2024 14:24:36 [57840, WinNUT]: New Icon Value For Systray : 1216
13/03/2024 14:24:36 [57840, WinNUT]: New Icon Value For Gui : 1216
13/03/2024 14:24:36 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Not Connected
13/03/2024 14:24:36 [57840, WinNUT]: Battery Status => Unknown
13/03/2024 14:24:36 [57840, WinNUT]: Disconnected from Nut Host
13/03/2024 14:24:36 [57840, String]: New Log to CB_Current Log : Disconnected from Nut Host
13/03/2024 14:24:36 [57840, WinNUT]: Client UPS_Connect subroutine beginning.
13/03/2024 14:24:36 [57840, UPS_Device]: Beginning connection: I9PUzKl3aLU=@192.168.10.1:3493, Name: ups [AutoReconnect]
13/03/2024 14:24:36 [57840, Nut_Socket]: Attempting TCP socket connection to 192.168.10.1:3493...
13/03/2024 14:24:36 [57840, Nut_Socket]: Connection established and streams ready for 192.168.10.1:3493
13/03/2024 14:24:36 [57840, Nut_Socket]: Attempting authentication...
13/03/2024 14:24:36 [57840, Nut_Socket]: Error while attempting to log in: INVALIDARGUMENT (ERR INVALID-ARGUMENT)
Query: USERNAME I9PUzKl3aLU=
13/03/2024 14:24:36 [57840, Nut_Socket]: NUT server reports VER: DSM6-2-25510-201118 NETVER: 1.2
13/03/2024 14:24:36 [57840, UPS_Device]: Retrieving basic UPS product information...
13/03/2024 14:24:36 [57840, UPS_Device]: ups.firmware is not supported by server.
13/03/2024 14:24:36 [57840, UPS_Device]: Apply Fallback Value when retrieving ups.firmware
13/03/2024 14:24:36 [57840, UPS_Device]: Determining best method to calculate power usage...
13/03/2024 14:24:36 [57840, UPS_Device]: ups.realpower is not supported by server.
13/03/2024 14:24:36 [57840, UPS_Device]: Unhandled error while getting ups.realpower
13/03/2024 14:24:36 [57840, UPS_Device]: Using NominalPowerCalc method to calculate power usage.
13/03/2024 14:24:36 [57840, UPS_Device]: battery.capacity is not supported by server.
13/03/2024 14:24:36 [57840, UPS_Device]: Apply Fallback Value when retrieving battery.capacity
13/03/2024 14:24:36 [57840, UPS_Device]: output.frequency.nominal is not supported by server.
13/03/2024 14:24:36 [57840, UPS_Device]: Apply Fallback Value when retrieving output.frequency.nominal
13/03/2024 14:24:36 [57840, UPS_Device]: Completed retrieval of basic UPS product information.
13/03/2024 14:24:36 [57840, WinNUT]: ups has indicated it's ready to start sending data.
13/03/2024 14:24:36 [57840, WinNUT]: Update Icon
13/03/2024 14:24:36 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
13/03/2024 14:24:36 [57840, WinNUT]: Connection to Nut Host Established
13/03/2024 14:24:36 [57840, String]: New Log to CB_Current Log : Connection to Nut Host 192.168.10.1:3493 Established
13/03/2024 14:24:36 [57840, WinNUT]: WinNut Preferences Applied.
13/03/2024 14:24:36 [57840, String]: New Log to CB_Current Log : WinNut Preferences Changed
13/03/2024 14:24:37 [57840, UPS_Device]: Enter Retrieve_UPS_Datas
13/03/2024 14:24:37 [57840, UPS_Device]: output.frequency is not supported by server.
13/03/2024 14:24:37 [57840, UPS_Device]: Apply Fallback Value when retrieving output.frequency
13/03/2024 14:24:37 [57840, UPS_Device]: input.frequency is not supported by server.
13/03/2024 14:24:37 [57840, UPS_Device]: Apply Fallback Value when retrieving input.frequency
13/03/2024 14:24:37 [57840, UPS_Device]: output.voltage is not supported by server.
13/03/2024 14:24:37 [57840, UPS_Device]: Apply Fallback Value when retrieving output.voltage
13/03/2024 14:24:37 [57840, UPS_Device]: UPS statuses have CHANGED...
13/03/2024 14:24:37 [57840, UPS_Device]: Current statuses: OL,CHRG
13/03/2024 14:24:37 [57840, WinNUT]: Handling new UPS status(es)...
13/03/2024 14:24:37 [57840, WinNUT]: Updating UPS data for Form.
13/03/2024 14:24:37 [57840, WinNUT]: Updating battery icons based on charge percent: 97%
13/03/2024 14:24:37 [57840, WinNUT]: Calculated estimated remaining battery time: 01:01:41
13/03/2024 14:24:37 [57840, WinNUT]: Update Dial
13/03/2024 14:24:37 [57840, WinNUT]: Update Icon
13/03/2024 14:24:37 [57840, WinNUT]: Status Icon Changed
13/03/2024 14:24:37 [57840, WinNUT]: New Icon Value For Systray : 1136
13/03/2024 14:24:37 [57840, WinNUT]: New Icon Value For Gui : 1136
13/03/2024 14:24:37 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
On Line
Battery OK
13/03/2024 14:24:37 [57840, WinNUT]: Battery Status => Discharging
13/03/2024 14:24:38 [57840, UPS_Device]: Enter Retrieve_UPS_Datas
13/03/2024 14:24:38 [57840, UPS_Device]: output.frequency is not supported by server.
13/03/2024 14:24:38 [57840, UPS_Device]: Apply Fallback Value when retrieving output.frequency
13/03/2024 14:24:38 [57840, UPS_Device]: input.frequency is not supported by server.
13/03/2024 14:24:38 [57840, UPS_Device]: Apply Fallback Value when retrieving input.frequency
13/03/2024 14:24:38 [57840, UPS_Device]: output.voltage is not supported by server.
13/03/2024 14:24:38 [57840, UPS_Device]: Apply Fallback Value when retrieving output.voltage
13/03/2024 14:24:38 [57840, UPS_Device]: UPS statuses have not changed since last update, skipping.
13/03/2024 14:24:38 [57840, WinNUT]: Updating UPS data for Form.
13/03/2024 14:24:38 [57840, WinNUT]: Updating battery icons based on charge percent: 97%
13/03/2024 14:24:38 [57840, WinNUT]: Calculated estimated remaining battery time: 01:01:41
13/03/2024 14:24:38 [57840, WinNUT]: Update Dial
13/03/2024 14:24:38 [57840, WinNUT]: Update Icon
13/03/2024 14:24:38 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
On Line
Battery OK
13/03/2024 14:24:38 [57840, WinNUT]: Battery Status => Discharging
13/03/2024 14:24:39 [57840, Pref_Gui]: Save Parameters.
13/03/2024 14:24:39 [57840, Pref_Gui]: Pref_Gui Params Saved
13/03/2024 14:24:39 [57840, Pref_Gui]: Setting LogControl statuses.
13/03/2024 14:24:39 [57840, WinNUT]: Beginning WinNUT_PrefsChanged subroutine.
13/03/2024 14:24:39 [57840, Logger]: WinNUT Client 2.3.8834.24333 Log file init
==== History of 200 previous events ====
[1] 13/03/2024 14:24:28 [57840, UPS_Device]: output.voltage is not supported by server.
[2] 13/03/2024 14:24:28 [57840, UPS_Device]: Apply Fallback Value when retrieving output.voltage
[3] 13/03/2024 14:24:28 [57840, UPS_Device]: UPS statuses have not changed since last update, skipping.
[4] 13/03/2024 14:24:28 [57840, WinNUT]: Updating UPS data for Form.
[5] 13/03/2024 14:24:28 [57840, WinNUT]: Updating battery icons based on charge percent: 97%
[6] 13/03/2024 14:24:28 [57840, WinNUT]: Calculated estimated remaining battery time: 01:01:41
[7] 13/03/2024 14:24:28 [57840, WinNUT]: Update Dial
[8] 13/03/2024 14:24:28 [57840, WinNUT]: Update Icon
[9] 13/03/2024 14:24:28 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
On Line
Battery OK
[10] 13/03/2024 14:24:28 [57840, WinNUT]: Battery Status => Discharging
[11] 13/03/2024 14:24:29 [57840, UPS_Device]: Enter Retrieve_UPS_Datas
[12] 13/03/2024 14:24:29 [57840, UPS_Device]: output.frequency is not supported by server.
[13] 13/03/2024 14:24:29 [57840, UPS_Device]: Apply Fallback Value when retrieving output.frequency
[14] 13/03/2024 14:24:29 [57840, UPS_Device]: input.frequency is not supported by server.
[15] 13/03/2024 14:24:29 [57840, UPS_Device]: Apply Fallback Value when retrieving input.frequency
[16] 13/03/2024 14:24:29 [57840, UPS_Device]: output.voltage is not supported by server.
[17] 13/03/2024 14:24:29 [57840, UPS_Device]: Apply Fallback Value when retrieving output.voltage
[18] 13/03/2024 14:24:29 [57840, UPS_Device]: UPS statuses have not changed since last update, skipping.
[19] 13/03/2024 14:24:29 [57840, WinNUT]: Updating UPS data for Form.
[20] 13/03/2024 14:24:29 [57840, WinNUT]: Updating battery icons based on charge percent: 97%
[21] 13/03/2024 14:24:29 [57840, WinNUT]: Calculated estimated remaining battery time: 01:01:41
[22] 13/03/2024 14:24:29 [57840, WinNUT]: Update Dial
[23] 13/03/2024 14:24:29 [57840, WinNUT]: Update Icon
[24] 13/03/2024 14:24:29 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
On Line
Battery OK
[25] 13/03/2024 14:24:29 [57840, WinNUT]: Battery Status => Discharging
[26] 13/03/2024 14:24:30 [57840, UPS_Device]: Enter Retrieve_UPS_Datas
[27] 13/03/2024 14:24:30 [57840, UPS_Device]: output.frequency is not supported by server.
[28] 13/03/2024 14:24:30 [57840, UPS_Device]: Apply Fallback Value when retrieving output.frequency
[29] 13/03/2024 14:24:30 [57840, UPS_Device]: input.frequency is not supported by server.
[30] 13/03/2024 14:24:30 [57840, UPS_Device]: Apply Fallback Value when retrieving input.frequency
[31] 13/03/2024 14:24:30 [57840, UPS_Device]: output.voltage is not supported by server.
[32] 13/03/2024 14:24:30 [57840, UPS_Device]: Apply Fallback Value when retrieving output.voltage
[33] 13/03/2024 14:24:30 [57840, UPS_Device]: UPS statuses have not changed since last update, skipping.
[34] 13/03/2024 14:24:30 [57840, WinNUT]: Updating UPS data for Form.
[35] 13/03/2024 14:24:30 [57840, WinNUT]: Updating battery icons based on charge percent: 97%
[36] 13/03/2024 14:24:30 [57840, WinNUT]: Calculated estimated remaining battery time: 01:01:41
[37] 13/03/2024 14:24:30 [57840, WinNUT]: Update Dial
[38] 13/03/2024 14:24:30 [57840, WinNUT]: Update Icon
[39] 13/03/2024 14:24:30 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
On Line
Battery OK
[40] 13/03/2024 14:24:30 [57840, WinNUT]: Battery Status => Discharging
[41] 13/03/2024 14:24:31 [57840, UPS_Device]: Enter Retrieve_UPS_Datas
[42] 13/03/2024 14:24:31 [57840, UPS_Device]: output.frequency is not supported by server.
[43] 13/03/2024 14:24:31 [57840, UPS_Device]: Apply Fallback Value when retrieving output.frequency
[44] 13/03/2024 14:24:31 [57840, UPS_Device]: input.frequency is not supported by server.
[45] 13/03/2024 14:24:31 [57840, UPS_Device]: Apply Fallback Value when retrieving input.frequency
[46] 13/03/2024 14:24:31 [57840, UPS_Device]: output.voltage is not supported by server.
[47] 13/03/2024 14:24:31 [57840, UPS_Device]: Apply Fallback Value when retrieving output.voltage
[48] 13/03/2024 14:24:31 [57840, UPS_Device]: UPS statuses have not changed since last update, skipping.
[49] 13/03/2024 14:24:31 [57840, WinNUT]: Updating UPS data for Form.
[50] 13/03/2024 14:24:31 [57840, WinNUT]: Updating battery icons based on charge percent: 97%
[51] 13/03/2024 14:24:31 [57840, WinNUT]: Calculated estimated remaining battery time: 01:01:41
[52] 13/03/2024 14:24:31 [57840, WinNUT]: Update Dial
[53] 13/03/2024 14:24:31 [57840, WinNUT]: Update Icon
[54] 13/03/2024 14:24:31 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
On Line
Battery OK
[55] 13/03/2024 14:24:31 [57840, WinNUT]: Battery Status => Discharging
[56] 13/03/2024 14:24:32 [57840, UPS_Device]: Enter Retrieve_UPS_Datas
[57] 13/03/2024 14:24:32 [57840, UPS_Device]: output.frequency is not supported by server.
[58] 13/03/2024 14:24:32 [57840, UPS_Device]: Apply Fallback Value when retrieving output.frequency
[59] 13/03/2024 14:24:32 [57840, UPS_Device]: input.frequency is not supported by server.
[60] 13/03/2024 14:24:32 [57840, UPS_Device]: Apply Fallback Value when retrieving input.frequency
[61] 13/03/2024 14:24:32 [57840, UPS_Device]: output.voltage is not supported by server.
[62] 13/03/2024 14:24:32 [57840, UPS_Device]: Apply Fallback Value when retrieving output.voltage
[63] 13/03/2024 14:24:32 [57840, UPS_Device]: UPS statuses have not changed since last update, skipping.
[64] 13/03/2024 14:24:32 [57840, WinNUT]: Updating UPS data for Form.
[65] 13/03/2024 14:24:32 [57840, WinNUT]: Updating battery icons based on charge percent: 97%
[66] 13/03/2024 14:24:32 [57840, WinNUT]: Calculated estimated remaining battery time: 01:01:41
[67] 13/03/2024 14:24:32 [57840, WinNUT]: Update Dial
[68] 13/03/2024 14:24:32 [57840, WinNUT]: Update Icon
[69] 13/03/2024 14:24:32 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
On Line
Battery OK
[70] 13/03/2024 14:24:32 [57840, WinNUT]: Battery Status => Discharging
[71] 13/03/2024 14:24:33 [57840, UPS_Device]: Enter Retrieve_UPS_Datas
[72] 13/03/2024 14:24:33 [57840, UPS_Device]: output.frequency is not supported by server.
[73] 13/03/2024 14:24:33 [57840, UPS_Device]: Apply Fallback Value when retrieving output.frequency
[74] 13/03/2024 14:24:33 [57840, UPS_Device]: input.frequency is not supported by server.
[75] 13/03/2024 14:24:33 [57840, UPS_Device]: Apply Fallback Value when retrieving input.frequency
[76] 13/03/2024 14:24:33 [57840, UPS_Device]: output.voltage is not supported by server.
[77] 13/03/2024 14:24:33 [57840, UPS_Device]: Apply Fallback Value when retrieving output.voltage
[78] 13/03/2024 14:24:33 [57840, UPS_Device]: UPS statuses have not changed since last update, skipping.
[79] 13/03/2024 14:24:33 [57840, WinNUT]: Updating UPS data for Form.
[80] 13/03/2024 14:24:33 [57840, WinNUT]: Updating battery icons based on charge percent: 97%
[81] 13/03/2024 14:24:33 [57840, WinNUT]: Calculated estimated remaining battery time: 01:01:41
[82] 13/03/2024 14:24:33 [57840, WinNUT]: Update Dial
[83] 13/03/2024 14:24:33 [57840, WinNUT]: Update Icon
[84] 13/03/2024 14:24:33 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
On Line
Battery OK
[85] 13/03/2024 14:24:33 [57840, WinNUT]: Battery Status => Discharging
[86] 13/03/2024 14:24:34 [57840, UPS_Device]: Enter Retrieve_UPS_Datas
[87] 13/03/2024 14:24:34 [57840, UPS_Device]: output.frequency is not supported by server.
[88] 13/03/2024 14:24:34 [57840, UPS_Device]: Apply Fallback Value when retrieving output.frequency
[89] 13/03/2024 14:24:34 [57840, UPS_Device]: input.frequency is not supported by server.
[90] 13/03/2024 14:24:34 [57840, UPS_Device]: Apply Fallback Value when retrieving input.frequency
[91] 13/03/2024 14:24:34 [57840, UPS_Device]: output.voltage is not supported by server.
[92] 13/03/2024 14:24:34 [57840, UPS_Device]: Apply Fallback Value when retrieving output.voltage
[93] 13/03/2024 14:24:34 [57840, UPS_Device]: UPS statuses have not changed since last update, skipping.
[94] 13/03/2024 14:24:34 [57840, WinNUT]: Updating UPS data for Form.
[95] 13/03/2024 14:24:34 [57840, WinNUT]: Updating battery icons based on charge percent: 97%
[96] 13/03/2024 14:24:34 [57840, WinNUT]: Calculated estimated remaining battery time: 01:01:41
[97] 13/03/2024 14:24:34 [57840, WinNUT]: Update Dial
[98] 13/03/2024 14:24:34 [57840, WinNUT]: Update Icon
[99] 13/03/2024 14:24:34 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
On Line
Battery OK
[100] 13/03/2024 14:24:34 [57840, WinNUT]: Battery Status => Discharging
[101] 13/03/2024 14:24:34 [57840, Pref_Gui]: Setting LogControl statuses.
[102] 13/03/2024 14:24:35 [57840, UPS_Device]: Enter Retrieve_UPS_Datas
[103] 13/03/2024 14:24:35 [57840, UPS_Device]: output.frequency is not supported by server.
[104] 13/03/2024 14:24:35 [57840, UPS_Device]: Apply Fallback Value when retrieving output.frequency
[105] 13/03/2024 14:24:35 [57840, UPS_Device]: input.frequency is not supported by server.
[106] 13/03/2024 14:24:35 [57840, UPS_Device]: Apply Fallback Value when retrieving input.frequency
[107] 13/03/2024 14:24:35 [57840, UPS_Device]: output.voltage is not supported by server.
[108] 13/03/2024 14:24:35 [57840, UPS_Device]: Apply Fallback Value when retrieving output.voltage
[109] 13/03/2024 14:24:35 [57840, UPS_Device]: UPS statuses have not changed since last update, skipping.
[110] 13/03/2024 14:24:35 [57840, WinNUT]: Updating UPS data for Form.
[111] 13/03/2024 14:24:35 [57840, WinNUT]: Updating battery icons based on charge percent: 97%
[112] 13/03/2024 14:24:35 [57840, WinNUT]: Calculated estimated remaining battery time: 01:01:41
[113] 13/03/2024 14:24:35 [57840, WinNUT]: Update Dial
[114] 13/03/2024 14:24:35 [57840, WinNUT]: Update Icon
[115] 13/03/2024 14:24:35 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
On Line
Battery OK
[116] 13/03/2024 14:24:35 [57840, WinNUT]: Battery Status => Discharging
[117] 13/03/2024 14:24:35 [57840, Pref_Gui]: Save Parameters.
[118] 13/03/2024 14:24:35 [57840, Pref_Gui]: WinNUT Added to Startup.
[119] 13/03/2024 14:24:35 [57840, Pref_Gui]: Pref_Gui Params Saved
[120] 13/03/2024 14:24:35 [57840, Pref_Gui]: Setting LogControl statuses.
[121] 13/03/2024 14:24:35 [57840, WinNUT]: Beginning WinNUT_PrefsChanged subroutine.
[122] 13/03/2024 14:24:35 [57840, Logger]: WinNUT Client 2.3.8834.24333 Log file init
[123] 13/03/2024 14:24:36 [57840, WinNUT]: Connection parameters Changed. Force Reconnect
[124] 13/03/2024 14:24:36 [57840, WinNUT]: Running Client disconnect subroutine.
[125] 13/03/2024 14:24:36 [57840, UPS_Device]: Processing request to disconnect...
[126] 13/03/2024 14:24:36 [57840, WinNUT]: Update all informations displayed to empty values
[127] 13/03/2024 14:24:36 [57840, WinNUT]: Update Icon
[128] 13/03/2024 14:24:36 [57840, WinNUT]: Status Icon Changed
[129] 13/03/2024 14:24:36 [57840, WinNUT]: New Icon Value For Systray : 1216
[130] 13/03/2024 14:24:36 [57840, WinNUT]: New Icon Value For Gui : 1216
[131] 13/03/2024 14:24:36 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Not Connected
[132] 13/03/2024 14:24:36 [57840, WinNUT]: Battery Status => Unknown
[133] 13/03/2024 14:24:36 [57840, WinNUT]: Disconnected from Nut Host
[134] 13/03/2024 14:24:36 [57840, String]: New Log to CB_Current Log : Disconnected from Nut Host
[135] 13/03/2024 14:24:36 [57840, WinNUT]: Client UPS_Connect subroutine beginning.
[136] 13/03/2024 14:24:36 [57840, UPS_Device]: Beginning connection: I9PUzKl3aLU=@192.168.10.1:3493, Name: ups [AutoReconnect]
[137] 13/03/2024 14:24:36 [57840, Nut_Socket]: Attempting TCP socket connection to 192.168.10.1:3493...
[138] 13/03/2024 14:24:36 [57840, Nut_Socket]: Connection established and streams ready for 192.168.10.1:3493
[139] 13/03/2024 14:24:36 [57840, Nut_Socket]: Attempting authentication...
[140] 13/03/2024 14:24:36 [57840, Nut_Socket]: Error while attempting to log in: INVALIDARGUMENT (ERR INVALID-ARGUMENT)
Query: USERNAME I9PUzKl3aLU=
[141] 13/03/2024 14:24:36 [57840, Nut_Socket]: NUT server reports VER: DSM6-2-25510-201118 NETVER: 1.2
[142] 13/03/2024 14:24:36 [57840, UPS_Device]: Retrieving basic UPS product information...
[143] 13/03/2024 14:24:36 [57840, UPS_Device]: ups.firmware is not supported by server.
[144] 13/03/2024 14:24:36 [57840, UPS_Device]: Apply Fallback Value when retrieving ups.firmware
[145] 13/03/2024 14:24:36 [57840, UPS_Device]: Determining best method to calculate power usage...
[146] 13/03/2024 14:24:36 [57840, UPS_Device]: ups.realpower is not supported by server.
[147] 13/03/2024 14:24:36 [57840, UPS_Device]: Unhandled error while getting ups.realpower
[148] 13/03/2024 14:24:36 [57840, UPS_Device]: Using NominalPowerCalc method to calculate power usage.
[149] 13/03/2024 14:24:36 [57840, UPS_Device]: battery.capacity is not supported by server.
[150] 13/03/2024 14:24:36 [57840, UPS_Device]: Apply Fallback Value when retrieving battery.capacity
[151] 13/03/2024 14:24:36 [57840, UPS_Device]: output.frequency.nominal is not supported by server.
[152] 13/03/2024 14:24:36 [57840, UPS_Device]: Apply Fallback Value when retrieving output.frequency.nominal
[153] 13/03/2024 14:24:36 [57840, UPS_Device]: Completed retrieval of basic UPS product information.
[154] 13/03/2024 14:24:36 [57840, WinNUT]: ups has indicated it's ready to start sending data.
[155] 13/03/2024 14:24:36 [57840, WinNUT]: Update Icon
[156] 13/03/2024 14:24:36 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
[157] 13/03/2024 14:24:36 [57840, WinNUT]: Connection to Nut Host Established
[158] 13/03/2024 14:24:36 [57840, String]: New Log to CB_Current Log : Connection to Nut Host 192.168.10.1:3493 Established
[159] 13/03/2024 14:24:36 [57840, WinNUT]: WinNut Preferences Applied.
[160] 13/03/2024 14:24:36 [57840, String]: New Log to CB_Current Log : WinNut Preferences Changed
[161] 13/03/2024 14:24:37 [57840, UPS_Device]: Enter Retrieve_UPS_Datas
[162] 13/03/2024 14:24:37 [57840, UPS_Device]: output.frequency is not supported by server.
[163] 13/03/2024 14:24:37 [57840, UPS_Device]: Apply Fallback Value when retrieving output.frequency
[164] 13/03/2024 14:24:37 [57840, UPS_Device]: input.frequency is not supported by server.
[165] 13/03/2024 14:24:37 [57840, UPS_Device]: Apply Fallback Value when retrieving input.frequency
[166] 13/03/2024 14:24:37 [57840, UPS_Device]: output.voltage is not supported by server.
[167] 13/03/2024 14:24:37 [57840, UPS_Device]: Apply Fallback Value when retrieving output.voltage
[168] 13/03/2024 14:24:37 [57840, UPS_Device]: UPS statuses have CHANGED...
[169] 13/03/2024 14:24:37 [57840, UPS_Device]: Current statuses: OL,CHRG
[170] 13/03/2024 14:24:37 [57840, WinNUT]: Handling new UPS status(es)...
[171] 13/03/2024 14:24:37 [57840, WinNUT]: Updating UPS data for Form.
[172] 13/03/2024 14:24:37 [57840, WinNUT]: Updating battery icons based on charge percent: 97%
[173] 13/03/2024 14:24:37 [57840, WinNUT]: Calculated estimated remaining battery time: 01:01:41
[174] 13/03/2024 14:24:37 [57840, WinNUT]: Update Dial
[175] 13/03/2024 14:24:37 [57840, WinNUT]: Update Icon
[176] 13/03/2024 14:24:37 [57840, WinNUT]: Status Icon Changed
[177] 13/03/2024 14:24:37 [57840, WinNUT]: New Icon Value For Systray : 1136
[178] 13/03/2024 14:24:37 [57840, WinNUT]: New Icon Value For Gui : 1136
[179] 13/03/2024 14:24:37 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
On Line
Battery OK
[180] 13/03/2024 14:24:37 [57840, WinNUT]: Battery Status => Discharging
[181] 13/03/2024 14:24:38 [57840, UPS_Device]: Enter Retrieve_UPS_Datas
[182] 13/03/2024 14:24:38 [57840, UPS_Device]: output.frequency is not supported by server.
[183] 13/03/2024 14:24:38 [57840, UPS_Device]: Apply Fallback Value when retrieving output.frequency
[184] 13/03/2024 14:24:38 [57840, UPS_Device]: input.frequency is not supported by server.
[185] 13/03/2024 14:24:38 [57840, UPS_Device]: Apply Fallback Value when retrieving input.frequency
[186] 13/03/2024 14:24:38 [57840, UPS_Device]: output.voltage is not supported by server.
[187] 13/03/2024 14:24:38 [57840, UPS_Device]: Apply Fallback Value when retrieving output.voltage
[188] 13/03/2024 14:24:38 [57840, UPS_Device]: UPS statuses have not changed since last update, skipping.
[189] 13/03/2024 14:24:38 [57840, WinNUT]: Updating UPS data for Form.
[190] 13/03/2024 14:24:38 [57840, WinNUT]: Updating battery icons based on charge percent: 97%
[191] 13/03/2024 14:24:38 [57840, WinNUT]: Calculated estimated remaining battery time: 01:01:41
[192] 13/03/2024 14:24:38 [57840, WinNUT]: Update Dial
[193] 13/03/2024 14:24:38 [57840, WinNUT]: Update Icon
[194] 13/03/2024 14:24:38 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
On Line
Battery OK
[195] 13/03/2024 14:24:38 [57840, WinNUT]: Battery Status => Discharging
[196] 13/03/2024 14:24:39 [57840, Pref_Gui]: Save Parameters.
[197] 13/03/2024 14:24:39 [57840, Pref_Gui]: Pref_Gui Params Saved
[198] 13/03/2024 14:24:39 [57840, Pref_Gui]: Setting LogControl statuses.
[199] 13/03/2024 14:24:39 [57840, WinNUT]: Beginning WinNUT_PrefsChanged subroutine.
[200] 13/03/2024 14:24:39 [57840, Logger]: WinNUT Client 2.3.8834.24333 Log file init
==== Begin Live Log ====
13/03/2024 14:24:39 [57840, WinNUT]: Connection parameters Changed. Force Reconnect
13/03/2024 14:24:39 [57840, WinNUT]: Running Client disconnect subroutine.
13/03/2024 14:24:39 [57840, UPS_Device]: Processing request to disconnect...
13/03/2024 14:24:39 [57840, WinNUT]: Update all informations displayed to empty values
13/03/2024 14:24:39 [57840, WinNUT]: Update Icon
13/03/2024 14:24:39 [57840, WinNUT]: Status Icon Changed
13/03/2024 14:24:39 [57840, WinNUT]: New Icon Value For Systray : 1216
13/03/2024 14:24:39 [57840, WinNUT]: New Icon Value For Gui : 1216
13/03/2024 14:24:39 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Not Connected
13/03/2024 14:24:39 [57840, WinNUT]: Battery Status => Unknown
13/03/2024 14:24:39 [57840, WinNUT]: Disconnected from Nut Host
13/03/2024 14:24:39 [57840, String]: New Log to CB_Current Log : Disconnected from Nut Host
13/03/2024 14:24:39 [57840, WinNUT]: Client UPS_Connect subroutine beginning.
13/03/2024 14:24:39 [57840, UPS_Device]: Beginning connection: I9PUzKl3aLU=@192.168.10.1:3493, Name: ups [AutoReconnect]
13/03/2024 14:24:39 [57840, Nut_Socket]: Attempting TCP socket connection to 192.168.10.1:3493...
13/03/2024 14:24:39 [57840, Nut_Socket]: Connection established and streams ready for 192.168.10.1:3493
13/03/2024 14:24:39 [57840, Nut_Socket]: Attempting authentication...
13/03/2024 14:24:39 [57840, Nut_Socket]: Error while attempting to log in: INVALIDARGUMENT (ERR INVALID-ARGUMENT)
Query: USERNAME I9PUzKl3aLU=
13/03/2024 14:24:39 [57840, Nut_Socket]: NUT server reports VER: DSM6-2-25510-201118 NETVER: 1.2
13/03/2024 14:24:39 [57840, UPS_Device]: Retrieving basic UPS product information...
13/03/2024 14:24:39 [57840, UPS_Device]: ups.firmware is not supported by server.
13/03/2024 14:24:39 [57840, UPS_Device]: Apply Fallback Value when retrieving ups.firmware
13/03/2024 14:24:39 [57840, UPS_Device]: Determining best method to calculate power usage...
13/03/2024 14:24:39 [57840, UPS_Device]: ups.realpower is not supported by server.
13/03/2024 14:24:39 [57840, UPS_Device]: Unhandled error while getting ups.realpower
13/03/2024 14:24:39 [57840, UPS_Device]: Using NominalPowerCalc method to calculate power usage.
13/03/2024 14:24:39 [57840, UPS_Device]: battery.capacity is not supported by server.
13/03/2024 14:24:39 [57840, UPS_Device]: Apply Fallback Value when retrieving battery.capacity
13/03/2024 14:24:39 [57840, UPS_Device]: output.frequency.nominal is not supported by server.
13/03/2024 14:24:39 [57840, UPS_Device]: Apply Fallback Value when retrieving output.frequency.nominal
13/03/2024 14:24:39 [57840, UPS_Device]: Completed retrieval of basic UPS product information.
13/03/2024 14:24:39 [57840, WinNUT]: ups has indicated it's ready to start sending data.
13/03/2024 14:24:39 [57840, WinNUT]: Update Icon
13/03/2024 14:24:39 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
13/03/2024 14:24:39 [57840, WinNUT]: Connection to Nut Host Established
13/03/2024 14:24:39 [57840, String]: New Log to CB_Current Log : Connection to Nut Host 192.168.10.1:3493 Established
13/03/2024 14:24:39 [57840, WinNUT]: WinNut Preferences Applied.
13/03/2024 14:24:39 [57840, String]: New Log to CB_Current Log : WinNut Preferences Changed
13/03/2024 14:24:39 [57840, WinNUT]: Main GUI activated.
13/03/2024 14:24:39 [57840, WinNUT]: Update Icon
13/03/2024 14:24:40 [57840, UPS_Device]: Enter Retrieve_UPS_Datas
13/03/2024 14:24:40 [57840, UPS_Device]: output.frequency is not supported by server.
13/03/2024 14:24:40 [57840, UPS_Device]: Apply Fallback Value when retrieving output.frequency
13/03/2024 14:24:40 [57840, UPS_Device]: input.frequency is not supported by server.
13/03/2024 14:24:40 [57840, UPS_Device]: Apply Fallback Value when retrieving input.frequency
13/03/2024 14:24:40 [57840, UPS_Device]: output.voltage is not supported by server.
13/03/2024 14:24:40 [57840, UPS_Device]: Apply Fallback Value when retrieving output.voltage
13/03/2024 14:24:40 [57840, UPS_Device]: UPS statuses have CHANGED...
13/03/2024 14:24:40 [57840, UPS_Device]: Current statuses: OL,CHRG
13/03/2024 14:24:40 [57840, WinNUT]: Handling new UPS status(es)...
13/03/2024 14:24:40 [57840, WinNUT]: Updating UPS data for Form.
13/03/2024 14:24:40 [57840, WinNUT]: Updating battery icons based on charge percent: 97%
13/03/2024 14:24:40 [57840, WinNUT]: Calculated estimated remaining battery time: 01:01:41
13/03/2024 14:24:40 [57840, WinNUT]: Update Dial
13/03/2024 14:24:40 [57840, WinNUT]: Update Icon
13/03/2024 14:24:40 [57840, WinNUT]: Status Icon Changed
13/03/2024 14:24:40 [57840, WinNUT]: New Icon Value For Systray : 1136
13/03/2024 14:24:40 [57840, WinNUT]: New Icon Value For Gui : 1072
13/03/2024 14:24:40 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
On Line
Battery OK
13/03/2024 14:24:40 [57840, WinNUT]: Battery Status => Discharging
13/03/2024 14:24:41 [57840, UPS_Device]: Enter Retrieve_UPS_Datas
13/03/2024 14:24:41 [57840, UPS_Device]: output.frequency is not supported by server.
13/03/2024 14:24:41 [57840, UPS_Device]: Apply Fallback Value when retrieving output.frequency
13/03/2024 14:24:41 [57840, UPS_Device]: input.frequency is not supported by server.
13/03/2024 14:24:41 [57840, UPS_Device]: Apply Fallback Value when retrieving input.frequency
13/03/2024 14:24:41 [57840, UPS_Device]: output.voltage is not supported by server.
13/03/2024 14:24:41 [57840, UPS_Device]: Apply Fallback Value when retrieving output.voltage
13/03/2024 14:24:41 [57840, UPS_Device]: UPS statuses have not changed since last update, skipping.
13/03/2024 14:24:41 [57840, WinNUT]: Updating UPS data for Form.
13/03/2024 14:24:41 [57840, WinNUT]: Updating battery icons based on charge percent: 97%
13/03/2024 14:24:41 [57840, WinNUT]: Calculated estimated remaining battery time: 01:01:41
13/03/2024 14:24:41 [57840, WinNUT]: Update Dial
13/03/2024 14:24:41 [57840, WinNUT]: Update Icon
13/03/2024 14:24:41 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
On Line
Battery OK
13/03/2024 14:24:41 [57840, WinNUT]: Battery Status => Discharging
13/03/2024 14:24:42 [57840, WinNUT]: Open Pref Gui From Menu
13/03/2024 14:24:42 [57840, Pref_Gui]: Load Pref Gui
13/03/2024 14:24:42 [57840, WinNUT]: Main Gui Lose Focus
13/03/2024 14:24:42 [57840, WinNUT]: Update Icon
13/03/2024 14:24:42 [57840, Pref_Gui]: Pref Gui Opened.
13/03/2024 14:24:42 [57840, UPS_Device]: Enter Retrieve_UPS_Datas
13/03/2024 14:24:42 [57840, UPS_Device]: output.frequency is not supported by server.
13/03/2024 14:24:42 [57840, UPS_Device]: Apply Fallback Value when retrieving output.frequency
13/03/2024 14:24:42 [57840, UPS_Device]: input.frequency is not supported by server.
13/03/2024 14:24:42 [57840, UPS_Device]: Apply Fallback Value when retrieving input.frequency
13/03/2024 14:24:42 [57840, UPS_Device]: output.voltage is not supported by server.
13/03/2024 14:24:42 [57840, UPS_Device]: Apply Fallback Value when retrieving output.voltage
13/03/2024 14:24:42 [57840, UPS_Device]: UPS statuses have not changed since last update, skipping.
13/03/2024 14:24:42 [57840, WinNUT]: Updating UPS data for Form.
13/03/2024 14:24:42 [57840, WinNUT]: Updating battery icons based on charge percent: 97%
13/03/2024 14:24:42 [57840, WinNUT]: Calculated estimated remaining battery time: 01:01:41
13/03/2024 14:24:42 [57840, WinNUT]: Update Dial
13/03/2024 14:24:42 [57840, WinNUT]: Update Icon
13/03/2024 14:24:42 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
On Line
Battery OK
13/03/2024 14:24:42 [57840, WinNUT]: Battery Status => Discharging
13/03/2024 14:24:43 [57840, UPS_Device]: Enter Retrieve_UPS_Datas
13/03/2024 14:24:43 [57840, UPS_Device]: output.frequency is not supported by server.
13/03/2024 14:24:43 [57840, UPS_Device]: Apply Fallback Value when retrieving output.frequency
13/03/2024 14:24:43 [57840, UPS_Device]: input.frequency is not supported by server.
13/03/2024 14:24:43 [57840, UPS_Device]: Apply Fallback Value when retrieving input.frequency
13/03/2024 14:24:43 [57840, UPS_Device]: output.voltage is not supported by server.
13/03/2024 14:24:43 [57840, UPS_Device]: Apply Fallback Value when retrieving output.voltage
13/03/2024 14:24:43 [57840, UPS_Device]: UPS statuses have not changed since last update, skipping.
13/03/2024 14:24:43 [57840, WinNUT]: Updating UPS data for Form.
13/03/2024 14:24:43 [57840, WinNUT]: Updating battery icons based on charge percent: 97%
13/03/2024 14:24:43 [57840, WinNUT]: Calculated estimated remaining battery time: 01:01:41
13/03/2024 14:24:43 [57840, WinNUT]: Update Dial
13/03/2024 14:24:43 [57840, WinNUT]: Update Icon
13/03/2024 14:24:43 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
On Line
Battery OK
13/03/2024 14:24:43 [57840, WinNUT]: Battery Status => Discharging
13/03/2024 14:24:44 [57840, UPS_Device]: Enter Retrieve_UPS_Datas
13/03/2024 14:24:44 [57840, UPS_Device]: output.frequency is not supported by server.
13/03/2024 14:24:44 [57840, UPS_Device]: Apply Fallback Value when retrieving output.frequency
13/03/2024 14:24:44 [57840, UPS_Device]: input.frequency is not supported by server.
13/03/2024 14:24:44 [57840, UPS_Device]: Apply Fallback Value when retrieving input.frequency
13/03/2024 14:24:44 [57840, UPS_Device]: output.voltage is not supported by server.
13/03/2024 14:24:44 [57840, UPS_Device]: Apply Fallback Value when retrieving output.voltage
13/03/2024 14:24:44 [57840, UPS_Device]: UPS statuses have not changed since last update, skipping.
13/03/2024 14:24:44 [57840, WinNUT]: Updating UPS data for Form.
13/03/2024 14:24:44 [57840, WinNUT]: Updating battery icons based on charge percent: 97%
13/03/2024 14:24:44 [57840, WinNUT]: Calculated estimated remaining battery time: 01:01:41
13/03/2024 14:24:44 [57840, WinNUT]: Update Dial
13/03/2024 14:24:44 [57840, WinNUT]: Update Icon
13/03/2024 14:24:44 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
On Line
Battery OK
13/03/2024 14:24:44 [57840, WinNUT]: Battery Status => Discharging
13/03/2024 14:24:45 [57840, UPS_Device]: Enter Retrieve_UPS_Datas
13/03/2024 14:24:45 [57840, UPS_Device]: output.frequency is not supported by server.
13/03/2024 14:24:45 [57840, UPS_Device]: Apply Fallback Value when retrieving output.frequency
13/03/2024 14:24:45 [57840, UPS_Device]: input.frequency is not supported by server.
13/03/2024 14:24:45 [57840, UPS_Device]: Apply Fallback Value when retrieving input.frequency
13/03/2024 14:24:45 [57840, UPS_Device]: output.voltage is not supported by server.
13/03/2024 14:24:45 [57840, UPS_Device]: Apply Fallback Value when retrieving output.voltage
13/03/2024 14:24:45 [57840, UPS_Device]: UPS statuses have not changed since last update, skipping.
13/03/2024 14:24:45 [57840, WinNUT]: Updating UPS data for Form.
13/03/2024 14:24:45 [57840, WinNUT]: Updating battery icons based on charge percent: 97%
13/03/2024 14:24:45 [57840, WinNUT]: Calculated estimated remaining battery time: 01:01:41
13/03/2024 14:24:45 [57840, WinNUT]: Update Dial
13/03/2024 14:24:45 [57840, WinNUT]: Update Icon
13/03/2024 14:24:45 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
On Line
Battery OK
13/03/2024 14:24:45 [57840, WinNUT]: Battery Status => Discharging
13/03/2024 14:24:45 [57840, Pref_Gui]: Setting LogControl statuses.
13/03/2024 14:24:46 [57840, UPS_Device]: Enter Retrieve_UPS_Datas
13/03/2024 14:24:46 [57840, UPS_Device]: output.frequency is not supported by server.
13/03/2024 14:24:46 [57840, UPS_Device]: Apply Fallback Value when retrieving output.frequency
13/03/2024 14:24:46 [57840, UPS_Device]: input.frequency is not supported by server.
13/03/2024 14:24:46 [57840, UPS_Device]: Apply Fallback Value when retrieving input.frequency
13/03/2024 14:24:46 [57840, UPS_Device]: output.voltage is not supported by server.
13/03/2024 14:24:46 [57840, UPS_Device]: Apply Fallback Value when retrieving output.voltage
13/03/2024 14:24:46 [57840, UPS_Device]: UPS statuses have not changed since last update, skipping.
13/03/2024 14:24:46 [57840, WinNUT]: Updating UPS data for Form.
13/03/2024 14:24:46 [57840, WinNUT]: Updating battery icons based on charge percent: 97%
13/03/2024 14:24:46 [57840, WinNUT]: Calculated estimated remaining battery time: 01:01:41
13/03/2024 14:24:46 [57840, WinNUT]: Update Dial
13/03/2024 14:24:46 [57840, WinNUT]: Update Icon
13/03/2024 14:24:46 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
On Line
Battery OK
13/03/2024 14:24:46 [57840, WinNUT]: Battery Status => Discharging
13/03/2024 14:24:47 [57840, UPS_Device]: Enter Retrieve_UPS_Datas
13/03/2024 14:24:47 [57840, UPS_Device]: output.frequency is not supported by server.
13/03/2024 14:24:47 [57840, UPS_Device]: Apply Fallback Value when retrieving output.frequency
13/03/2024 14:24:47 [57840, UPS_Device]: input.frequency is not supported by server.
13/03/2024 14:24:47 [57840, UPS_Device]: Apply Fallback Value when retrieving input.frequency
13/03/2024 14:24:47 [57840, UPS_Device]: output.voltage is not supported by server.
13/03/2024 14:24:47 [57840, UPS_Device]: Apply Fallback Value when retrieving output.voltage
13/03/2024 14:24:47 [57840, UPS_Device]: UPS statuses have not changed since last update, skipping.
13/03/2024 14:24:47 [57840, WinNUT]: Updating UPS data for Form.
13/03/2024 14:24:47 [57840, WinNUT]: Updating battery icons based on charge percent: 97%
13/03/2024 14:24:47 [57840, WinNUT]: Calculated estimated remaining battery time: 01:01:41
13/03/2024 14:24:47 [57840, WinNUT]: Update Dial
13/03/2024 14:24:47 [57840, WinNUT]: Update Icon
13/03/2024 14:24:47 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
On Line
Battery OK
13/03/2024 14:24:47 [57840, WinNUT]: Battery Status => Discharging
13/03/2024 14:24:48 [57840, UPS_Device]: Enter Retrieve_UPS_Datas
13/03/2024 14:24:48 [57840, UPS_Device]: output.frequency is not supported by server.
13/03/2024 14:24:48 [57840, UPS_Device]: Apply Fallback Value when retrieving output.frequency
13/03/2024 14:24:48 [57840, UPS_Device]: input.frequency is not supported by server.
13/03/2024 14:24:48 [57840, UPS_Device]: Apply Fallback Value when retrieving input.frequency
13/03/2024 14:24:48 [57840, UPS_Device]: output.voltage is not supported by server.
13/03/2024 14:24:48 [57840, UPS_Device]: Apply Fallback Value when retrieving output.voltage
13/03/2024 14:24:48 [57840, UPS_Device]: UPS statuses have not changed since last update, skipping.
13/03/2024 14:24:48 [57840, WinNUT]: Updating UPS data for Form.
13/03/2024 14:24:48 [57840, WinNUT]: Updating battery icons based on charge percent: 97%
13/03/2024 14:24:48 [57840, WinNUT]: Calculated estimated remaining battery time: 01:01:41
13/03/2024 14:24:48 [57840, WinNUT]: Update Dial
13/03/2024 14:24:48 [57840, WinNUT]: Update Icon
13/03/2024 14:24:48 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
On Line
Battery OK
13/03/2024 14:24:48 [57840, WinNUT]: Battery Status => Discharging
13/03/2024 14:24:49 [57840, UPS_Device]: Enter Retrieve_UPS_Datas
13/03/2024 14:24:49 [57840, UPS_Device]: output.frequency is not supported by server.
13/03/2024 14:24:49 [57840, UPS_Device]: Apply Fallback Value when retrieving output.frequency
13/03/2024 14:24:49 [57840, UPS_Device]: input.frequency is not supported by server.
13/03/2024 14:24:49 [57840, UPS_Device]: Apply Fallback Value when retrieving input.frequency
13/03/2024 14:24:49 [57840, UPS_Device]: output.voltage is not supported by server.
13/03/2024 14:24:49 [57840, UPS_Device]: Apply Fallback Value when retrieving output.voltage
13/03/2024 14:24:49 [57840, UPS_Device]: UPS statuses have not changed since last update, skipping.
13/03/2024 14:24:49 [57840, WinNUT]: Updating UPS data for Form.
13/03/2024 14:24:49 [57840, WinNUT]: Updating battery icons based on charge percent: 97%
13/03/2024 14:24:49 [57840, WinNUT]: Calculated estimated remaining battery time: 01:01:41
13/03/2024 14:24:49 [57840, WinNUT]: Update Dial
13/03/2024 14:24:49 [57840, WinNUT]: Update Icon
13/03/2024 14:24:49 [57840, WinNUT]: NotifyIcon Text => 
WinNUT Client - 2.3
Connected
On Line
Battery OK
13/03/2024 14:24:49 [57840, WinNUT]: Battery Status => Discharging
13/03/2024 14:24:49 [57840, Pref_Gui]: Show LogFile

EDIT: This may be a synology issue:

/var/log/ups.log
2024-03-13T15:03:52+01:00 NAS19 synoups: synoups online
2024-03-13T15:03:52+01:00 NAS19 synoups: =====log UPS status start=====
2024-03-13T15:03:52+01:00 NAS19 synoups: device.mfr=American Power Conversion
2024-03-13T15:03:52+01:00 NAS19 synoups: device.model=Back-UPS BX2200MI
2024-03-13T15:03:52+01:00 NAS19 synoups: battery.charge=99
2024-03-13T15:03:52+01:00 NAS19 synoups: battery.runtime=3777
2024-03-13T15:03:52+01:00 NAS19 synoups: battery.voltage=27.2
2024-03-13T15:03:52+01:00 NAS19 synoups: input.voltage=234.0
2024-03-13T15:03:52+01:00 NAS19 synoups: output.voltage=
2024-03-13T15:03:52+01:00 NAS19 synoups: ups.load=0
2024-03-13T15:03:52+01:00 NAS19 synoups: ups.status=OL CHRG
2024-03-13T15:03:52+01:00 NAS19 synoups: =====log UPS status end=====

ups.load is 0 here as well. Not sure if it was correct here on the old UPS.

gbakeman commented 5 months ago

@Chainfire Sorry for taking awhile to get back to you, and glad you were able to get things working! ☺️ I changed the way WinNUT reports missing variables recently which I think took a lot of people by surprise, because previously WinNUT was reporting that everything was fine and present. Let us know if there's any other issues.

MaxMadcc commented 5 months ago
UPS variables ```HUAWEI01 (Huawei/UPS2000A/V2R1C1SPC40) battery.capacity (Battery capacity (Ah)) : 9 battery.charge (Battery charge (percent of full)) : 100.0 battery.charger.status (Battery charger status) : charging battery.packs (Number of battery packs) : 4 battery.runtime (Battery runtime (seconds)) : 2418 battery.voltage (Battery voltage (V)) : 54.4 device.mfr (Description unavailable) : Huawei device.model (Description unavailable) : UPS2000A device.serial (Description unavailable) : 2102290503HGJ7000056 device.type (Description unavailable) : ups driver.debug (Current debug verbosity level of the driver program) : 1 driver.flag.allow_killpower (Safety flip-switch to allow the driver daemon to send UPS shutdown command (accessible via driver.killpower)) : 0 driver.name (Driver name) : huawei-ups2000 driver.parameter.pollinterval (Description unavailable) : 3 driver.parameter.port (Description unavailable) : /dev/ttySVA100 driver.parameter.synchronous (Description unavailable) : no driver.state (Description unavailable) : updateinfo driver.version (Driver version - NUT release) : 2.8.1 driver.version.internal (Internal driver version) : 0.05 input.bypass.frequency (Description unavailable) : 50.0 input.bypass.voltage (Description unavailable) : 232.6 input.frequency (Input line frequency (Hz)) : 50.0 input.voltage (Input voltage (V)) : 232.6 output.current (Output current (A)) : 1.7 output.frequency (Output frequency (Hz)) : 50.0 output.power (Description unavailable) : 300.0 output.realpower (Description unavailable) : 200.0 output.voltage (Output voltage (V)) : 219.5 ups.beeper.status (UPS beeper status) : enabled ups.delay.reboot (Interval to wait before rebooting the UPS (seconds)) : 60 ups.delay.shutdown (Interval to wait after shutdown with delay command (seconds)) : 60 ups.delay.start (Interval to wait before (re)starting the load (seconds)) : 60 ups.firmware (UPS firmware) : V2R1C1SPC40 ups.firmware.aux (Auxiliary device firmware) : P1.0-D1.0 ups.load (Load on UPS (percent of full)) : 18.0 ups.mfr (UPS manufacturer) : Huawei ups.model (UPS model) : UPS2000A ups.power.nominal (UPS power rating (VA)) : 2000 ups.serial (UPS serial number) : 21 ups.status (UPS status) : OL CHRG ups.temperature (UPS temperature (degrees C)) : 28.4 ups.timer.reboot (Time before the load will be rebooted (seconds)) : -1 ups.timer.shutdown (Time before the load will be shutdown (seconds)) : -1 ups.timer.start (Time before the load will be started (seconds)) : -1 ups.type (UPS type) : online ```

The output power should be calculated according to the following. P = I V 0.8(note: Power Factor)

It appears that my UPS variables include output.realpower and output.power, but the the load wattage graph show 0W and percentage of real power.

gbakeman commented 5 months ago

UPS variables

The output power should be calculated according to the following. P = I*V

It appears that my UPS variables include output.realpower and output.power, but the the load wattage graph show 0W and percentage of real power.

Would you please include your WinNUT log as an attachment?

MaxMadcc commented 5 months ago

UPS variables The output power should be calculated according to the following. P = I*V It appears that my UPS variables include output.realpower and output.power, but the the load wattage graph show 0W and percentage of real power.

Would you please include your WinNUT log as an attachment?

Log (part) ```2024/4/28 23:06:08 [30336, Nut_Socket]: Attempting authentication... 2024/4/28 23:06:08 [30336, Nut_Socket]: NUT server reports VER: 2.8.1 NETVER: 2024/4/28 23:06:08 [30336, UPS_Device]: Retrieving basic UPS product information... 2024/4/28 23:06:08 [30336, UPS_Device]: Determining best method to calculate power usage... 2024/4/28 23:06:08 [30336, UPS_Device]: ups.realpower is not supported by server. 2024/4/28 23:06:08 [30336, UPS_Device]: ups.realpower.nominal is not supported by server. 2024/4/28 23:06:08 [30336, UPS_Device]: input.current.nominal is not supported by server. 2024/4/28 23:06:08 [30336, UPS_Device]: Unable to find a suitable method to calculate power usage. 2024/4/28 23:06:08 [30336, UPS_Device]: output.frequency.nominal is not supported by server. 2024/4/28 23:06:08 [30336, UPS_Device]: Apply Fallback Value when retrieving output.frequency.nominal 2024/4/28 23:06:08 [30336, UPS_Device]: Completed retrieval of basic UPS product information. 2024/4/28 23:06:08 [30336, WinNUT]: Connection to Nut Host Established 2024/4/28 23:06:09 [30336, UPS_Device]: UPS statuses have CHANGED... 2024/4/28 23:06:09 [30336, UPS_Device]: Current statuses: OL,CHRG 2024/4/28 23:06:59 [30336, UPS_Device]: UPS device updating status is now [False] 2024/4/28 23:06:59 [30336, UPS_Device]: UPS device updating status is now [True] 2024/4/28 23:28:29 [30336, UPS_Device]: UPS device updating status is now [False] 2024/4/28 23:28:29 [30336, UPS_Device]: UPS device updating status is now [True] 2024/4/28 23:37:27 [30336, Pref_Gui]: Opened UI window to log location. 2024/4/28 23:37:39 [30336, WinNUT]: Disconnected from Nut Host 2024/4/28 23:37:39 [30336, WinNUT]: Client UPS_Connect subroutine beginning. ```

OK, It seems like I found where the problem is.

gbakeman commented 5 months ago

It sounds like I just haven't accounted for .power and .realpower vars yet. Do you know which one is actually the amount of power your UPS is consuming?

MaxMadcc commented 5 months ago

I took a look at the NUT (Network UPS Tools) driver source code.

https://github.com/networkupstools/nut/blob/9e029270d7914df27c9743c95aad219d7ea2e32e/drivers/huawei-ups2000.c#L552 https://github.com/networkupstools/nut/blob/9e029270d7914df27c9743c95aad219d7ea2e32e/drivers/huawei-ups2000.c#L553

.power is apparent power. .realpower is active power.

So .realpower is actually the amount of power my UPS is consuming.

gbakeman commented 5 months ago

@MaxMadcc I made a new issue for your UPS here (#150) since I'm not sure if OP is experiencing the exact same problem as you. Please go ahead and follow that issue. I'm not sure if you're already on it, but I'll make a branch and start working on a fix since I think it should be fairly easy.

ElGuillermo commented 4 months ago

Hi ! Same prob on a EATON ELLIPSE ECO 1200, hooked to an ASUSTOR NAS model AS-302T.

badly reported values :

All these values were correct on old WinNUT version (latest from the previous repo)

complete report :

battery.charge (Description unavailable) : 100
battery.charge.low (Description unavailable) : 20
battery.runtime (Description unavailable) : 1706
battery.type (Description unavailable) : PbAc
device.mfr (Description unavailable) : EATON
device.model (Description unavailable) : Ellipse ECO 1200
device.serial (Description unavailable) : 000000000
device.type (Description unavailable) : ups
driver.name (Description unavailable) : usbhid-ups
driver.parameter.pollfreq (Description unavailable) : 30
driver.parameter.pollinterval (Description unavailable) : 10
driver.parameter.port (Description unavailable) : /dev/ttyS1
driver.version (Description unavailable) : 2.7.2
driver.version.data (Description unavailable) : MGE HID 1.33
driver.version.internal (Description unavailable) : 0.38
input.transfer.high (Description unavailable) : 264
input.transfer.low (Description unavailable) : 184
outlet.1.desc (Description unavailable) : PowerShare Outlet 1
outlet.1.id (Description unavailable) : 2
outlet.1.status (Description unavailable) : on
outlet.1.switchable (Description unavailable) : no
outlet.2.desc (Description unavailable) : PowerShare Outlet 2
outlet.2.id (Description unavailable) : 3
outlet.2.status (Description unavailable) : on
outlet.2.switchable (Description unavailable) : no
outlet.desc (Description unavailable) : Main Outlet
outlet.id (Description unavailable) : 1
outlet.power (Description unavailable) : 25
outlet.switchable (Description unavailable) : no
output.frequency.nominal (Description unavailable) : 50
output.voltage (Description unavailable) : 230.0
output.voltage.nominal (Description unavailable) : 230
ups.beeper.status (Description unavailable) : enabled
ups.delay.shutdown (Description unavailable) : 20
ups.delay.start (Description unavailable) : 30
ups.firmware (Description unavailable) : 02
ups.load (Description unavailable) : 18
ups.mfr (Description unavailable) : EATON
ups.model (Description unavailable) : Ellipse ECO 1200
ups.power.nominal (Description unavailable) : 1200
ups.productid (Description unavailable) : ffff
ups.serial (Description unavailable) : 000000000
ups.status (Description unavailable) : OL CHRG
ups.timer.shutdown (Description unavailable) : -1
ups.timer.start (Description unavailable) : -1
ups.vendorid (Description unavailable) : 0463
gbakeman commented 4 months ago

Hi @ElGuillermo ,

Please see #136. Indeed, your NUT server isn't providing a battery voltage or input voltage - yours is only displaying output information in that regard. However, I'm not exactly sure why your UPS load isn't working. Please open a new discussion here with the info you've already provided, along with the WinNUT log file attached. Make sure your log level is set to Debug before doing so. Thank you for providing this info so far.