Remaing Time Unavalible Pc Shuts down imediatly #157

Closed FigJam23 closed 6 months ago

FigJam23 commented 6 months ago

WinNUT Version: 2.3.8892.2 Windows OS Version: w10

Describe the bug Remaining Time unknown on my Powersheild rt2000 and when power disconnects from ups winnut try's shutting down immediately

running on RPI using upsc powershield@192.168.1.200

######### Power Sheild UPS ###################
battery.charge: 100
battery.voltage: 54.70
battery.voltage.high: 52.00
battery.voltage.low: 41.60
battery.voltage.nominal: 48.0
device.mfr:
device.model: LIHVX2K0
device.type: ups
driver.name: blazer_usb
driver.parameter.pollinterval: 2
driver.parameter.port: auto
driver.parameter.productid: 5161
driver.parameter.synchronous: auto
driver.parameter.vendorid: 0665
driver.version: 2.8.0
driver.version.internal: 0.14
driver.version.usb: libusb-1.0.26 (API: 0x1000109)
input.current.nominal: 8.0
input.frequency: 50.0
input.frequency.nominal: 50
input.voltage: 231.3
input.voltage.fault: 231.2
input.voltage.nominal: 240
output.voltage: 231.2
ups.beeper.status: enabled
ups.delay.shutdown: 30
ups.delay.start: 180
ups.firmware: 00303.06
ups.load: 2
ups.mfr:
ups.model: LIHVX2K0
ups.productid: 5161
ups.status: OL
ups.temperature: 16.5
ups.type: offline / line interactive
ups.vendorid: 0665
admin@MikesNetMon:~ $

Using same cmd on my EATON ups seems to work

################ Eaton UPS ###################
admin@MikesNetMon:~ $ upsc eaton@192.168.1.200
Init SSL without certificate database
battery.charge: 100
battery.runtime: 2637
battery.type: PbAc
device.mfr: EATON
device.model: 5E 850i
device.type: ups
driver.name: usbhid-ups
driver.parameter.pollfreq: 30
driver.parameter.pollinterval: 2
driver.parameter.port: auto
driver.parameter.synchronous: auto
driver.version: 2.8.0
driver.version.data: MGE HID 1.46
driver.version.internal: 0.47
driver.version.usb: libusb-1.0.26 (API: 0x1000109)
input.voltage: 234.0
outlet.1.status: on
outlet.desc: Main Outlet
outlet.id: 1
outlet.switchable: no
output.frequency: 49.9
output.frequency.nominal: 50
output.voltage: 232.0
output.voltage.nominal: 230
ups.beeper.status: enabled
ups.delay.shutdown: 20
ups.firmware: 03.08.0018
ups.load: 9
ups.mfr: EATON
ups.model: 5E 850i
ups.power.nominal: 850
ups.productid: ffff
ups.realpower: 61
ups.start.battery: yes
ups.status: OL
ups.timer.shutdown: -1
ups.vendorid: 0463

so my Eaton ups works but the powersheild ups does not seem to its likely due to missing this battery.runtime: value. and the issue caused on Winnut shutting down my pc almost straight away is a problem how can I get this to work or get the battery.runtime: status from my powersheild ups. would anyone have any idea on how to resolve this or stop Winnut from shutting my PC down can't see an option to disable the shutdown either. Is it possible to just use the shutdown if lower than 5 percent?

FigJam23 commented 6 months ago

ups1

FigJam23 commented 6 months ago

ok i fixed my issue changed my usb driver from blazer_usb to nutdrv_qx and now have

admin@MikesNetMon:~ $ upsc powershield@192.168.1.200
Init SSL without certificate database
battery.charge: 94
battery.energysave: no
battery.packs: 1
battery.protection: yes
battery.runtime: 21180
battery.voltage: 54.70
battery.voltage.nominal: 48.0
device.model: LIHVX2K0
device.serial: 81201806100137
device.type: ups
driver.name: nutdrv_qx
driver.parameter.pollfreq: 30
driver.parameter.pollinterval: 2
driver.parameter.port: auto
driver.parameter.productid: 5161
driver.parameter.synchronous: auto
driver.parameter.vendorid: 0665
driver.version: 2.8.0
driver.version.data: Voltronic 0.06
driver.version.internal: 0.32
driver.version.usb: libusb-1.0.26 (API: 0x1000109)
input.current.nominal: 8.0
input.frequency: 50.1
input.frequency.nominal: 50.0
input.phases: 1
input.voltage: 231.4
input.voltage.nominal: 240.0
outlet.0.switchable: no
output.current: 0.2
output.current.nominal: 8
output.frequency: 50.1
output.frequency.nominal: 50.0
output.phases: 1
output.power.maximum.percent: 2
output.power.minimum.percent: 2
output.powerfactor: 0.8
output.voltage: 231.5
output.voltage.nominal: 240.0
ups.beeper.status: enabled
ups.delay.shutdown: 30
ups.delay.start: 180
ups.firmware: 00303.06
ups.firmware.aux: P00
ups.load: 2
ups.power.nominal: 2000
ups.productid: 5161
ups.start.auto: yes
ups.start.battery: yes
ups.status: OL
ups.temperature: 23.3
ups.type: line-interactive
ups.vendorid: 0665
admin@MikesNetMon:~ $
gbakeman commented 6 months ago

Thank you for posting back!