openWB / core

GNU General Public License v3.0
52 stars 68 forks source link

Set imported and exported en energy values for EvuKitFlex with SDM meters #1916

Closed dj3mu closed 1 week ago

dj3mu commented 1 week ago

Potentially adresses [Ticket #74832726]

The values for total imported and exported energy are not set at all when SDM meters (e.g. SDM630, SDM72 or SDM120) are being used as EvuKitFlex.

However I cannot test this as the above ticket is coming from one of our customers and I don't have a setup similar to customer available.

Please double-check carefully whether the fix is correct. I think SDMs do directly deliver the imported and exported energies so no special handling is required. Additionally I copied the current setting from the "else" path into the SDM path as currents have been working fine so far at customer's system.

LKuemmel commented 1 week ago

Die SDM Zähler arbeiten nicht saldierend. Import und Export müssen aber saldiert ermittelt werden. Deshalb werden die Werte nicht aus den Registern ausgelesen, sondern von der openWB berechnet. Beim Speicher- und PV-Kit werden die Werte aus den Registern ausgelesen, da dort kein Bezug und Einspeisung gleichzeitig auftreten können.