After some valid measurements, some sensors stop working as expected.
By observing the sensor power supply, it could get observed, that the power drops from 24 V to almost 0 V for a time of 600 ms.
The cause for this is not 100% clear, but it seams that the IO-Link-transceiver detected an over-current situation and disconnects the powering of the sensor.
To avoid this problems, the flag “LClimDis” should get removed from the method Max14819::begin