Replace Switch PSU + Fans with AFI version #1158

Open Firefishy opened 23 hours ago

Firefishy commented 23 hours ago

The switches at AMS blow heat in the wrong direction. This is causing a heat bubble due to hot air being continuously cycled through the servers and switches within the rack.

Per switch the following is required: 2x JPSU-350-AC-AFI 2x EX4300-FAN-AFI 660-044938 (Fan Module, Airflow In)

grischard commented 18 hours ago

Power consumption for context:

Switch1 dublin: 60W+55W and Switch2 dublin: 48W+49W.

We have no power monitoring per outlet in Amsterdam. The switches in AMS will be fractionally more anyway because we have the POE version (POE disabled).

mboeringa commented 43 minutes ago

Related: https://github.com/openstreetmap/operations/issues/1076