Open rob570 opened 10 months ago
I found those somewhere here in the discussions:
{0x63,8,105,2,1,"[HPSU] Mixed leaving water temperature after the tank R7T (DLWA2)"},
{0x63,10,101,1,-1,"[HPSU] Tank valve position (0:Bypass 100:Tank)"},
{0x63,11,101,1,-1,"[HPSU] Bypass valve position (0:Bypass 100:Emitter)"},
{0x20,0,105,2,1,"R6T"},
Dear Maromme and Ifrancke, thank you for helping and sharing. I'll try next week and I'll give you a feedback. Have a nice day, Roberto
Hi, I can confirm the settings provided work! Thank you for your reply. I attach a new definition file (renamed to csv) based on your information. ALTHERMA(ECH2O).h.csv Roberto
@lfrancke @rob570 why
{0x62,11,405,1,1,"Water pressure"},
and not
{0x62,11,105,1,1,"Water pressure"},
the conversion 405 is only for the R32 gas inside the refrigerant circuit.
Thank you Simone, That's why even after pulling the breaks on 405 conv ( https://github.com/raomin/ESPAltherma/pull/325 ) I've got wrong values. Grazie!
how many Italians with this heat pump!
~I am only missing the two 3-way valve values...~
Only Refrig. Temp. liquid side (R3T) is Wrong
Hi, I can't confirm the settings provided work! In my case: {0x62,11,405,1,1,"Pressione acqua"}, return Pressione acqua: -51.1813 (Daikin 1,3 Bar)
{0x62,11,105,1,1,"Pressione acqua"}, return Pressione acqua: 0 (Daikin 1,3 bar)
and:
{0x63,10,101,1,-1,"[HPSU] Tank valve position (0:Bypass 100:Tank)"}, {0x63,11,101,1,-1,"[HPSU] Bypass valve position (0:Bypass 100:Emitter)"},
[HPSU] Tank valve position (0:Bypass 100:Tank): 0 [HPSU] Bypass valve position (0:Bypass 100:Emitter): 0 (Daikin 12%)
Thank you
In my case:
{0x62,11,405,1,1,"Pressione acqua"}, return
Pressione acqua: -51.1813 (Daikin 1,3 Bar)
{0x62,11,105,1,1,"Pressione acqua"}, return
Pressione acqua: 0 (Daikin 1,3 bar)
Molto strano, a me torna il valore corretto
{0x63,10,101,1,-1,"[HPSU] Tank valve position (0:Bypass 100:Tank)"},
{0x63,11,101,1,-1,"[HPSU] Bypass valve position (0:Bypass 100:Emitter)"},
pure queste a me tornano corretti i valori, che modello di ECH2O hai?
Daikin Altherma 3 R ECH2O:
EHSXB08P30DA
vecchia elettronica, potrebbe essere molto diverso da quelli dalla serie nuova con eye
c'è roba da prendere con il connettore CAM
Hi to everyone and Thank you Raomin for your project. I've configured ESPAltherma for an Altherma 3 R ECH2O. I've used Top-Grade.h with two fixes. I'm not able to find the registry for querying:
Here what I fixed in the description:
Could anyone help me? Thank you, Roberto