Closed tuxianerDE closed 6 months ago
After manually changing the limit to 100%
Is it possible that the diff limit of 30W is too large and hence the INV did not trigger?
That was my thought too....
Issue resolved. Given the limit function & fixed interval in case no triggered received as a health check
I observed that today afternoon the sun - finally - came out behind the cloud. The inverter in this case did not increase the limit to better match the new direct irridation.
I manually entered in openDTU the limit of 100%, which directly increased the output of the INV accordingly. Afterwards the script properly picked the new limit out and steered it - supposedly correctly.
I have attached a graph showing that it is was not due to any interval limitation as the increased power was present long enough to get detected. Further I attached a screenshot from my DTU showing that the limit was maxed out by the output and yet the script did not trigger any acction up until I manually intervened.
solarflow-control-directpanel_increase.log