sbslab / BICEPS

Development and evaluation repository for the Biomimetic Integrated Community Energy and Power System (BICEPS)
Other
0 stars 1 forks source link

Thermal Zone Heat Balance #12

Closed khinkelman closed 2 years ago

khinkelman commented 2 years ago

The room maintains a temperature above the setpoint without any mass flow. Thus, the pumps/fans are not running. This is not correct.

image

khinkelman commented 2 years ago

Pump is "bottoming" out...

image

khinkelman commented 2 years ago

Problem in the u_m measured setpoint in the PI controller for the FCU fan. The measured u_m should be the room air temperature, but the measured temperature is not the same as the room air temperature. image

khinkelman commented 2 years ago

Relocated temperature sensor from fan downstream port to inlet port (from the room). image

khinkelman commented 2 years ago

Better, but measured temperature goes to fixed constant value when mass flow is zero. This is not correct. image