Closed martijndierckx closed 2 years ago
That is correct, it felt for us to be the safest setup. For example: with 2x 2P in parallel you could have 2 live fase wires without the neutral if for some reason the contactors aren't working/controlled correctly.
Below a complete setup when already having an existing installation and the EVSE is placed in a new cabinet. Of course, many variations are possible depending on local regulations. This setup at least was approved in Belgium. Some remarks:
Disclaimer: use at your own risk!
Can you confirm wiring for 2 contactors in order to switch between 1P and 3P charging should be like this? (If so, can you update the manual as well?)
Linked issue: #18