sfstar / hass-victron

Integration for Home Assistant to fetch data from the victron gx device via modbusTCP
Apache License 2.0
185 stars 29 forks source link

no feeding Power to grid / charging in Mode 3 and in Mode 2 #226

Open MmeHulot opened 3 months ago

MmeHulot commented 3 months ago

When going in ESS Mode 3 (EXTERNAL CONTROL) and Mode ON and setting number.victron_vebus_l1_acpowersetpoint_228 to a positive value e.g. +500W or a negative Value -300W the Multiplus starts inverting/charging for a short time and then stops and is going to passthru.

When set a value +500W/-300W in Mode 2 (KEEP_CHARGED) in number.victron_settings_ess_acpowersetpoint_0 the Multiplus does nothing.

What am i doing wrong? I just want to set a target value to make the Multiplus inverting/charging

Setup: Intervall is set to 10s, Multiplus is only connected to AC-in and Battery 48V, no energy meter connected, no BMS, Gateway: v3.41, VE.Bus: 552, Unit-ID: 228, 100

pos-ei-don commented 3 months ago

You need to resend number.victron_vebus_l1_acpowersetpoint_228 once In A Minute fore safety reasons

MmeHulot commented 3 months ago

after hours of trial and error. Mode 3 does not work. All those who want to control the Multiplus 2 with Homeassistant will find the settings in the PDF.

Funktionierende_Config_Einspeisen_Laden_2.pdf