Issue with switches after reconfiguration #2

Open phdumair opened 4 months ago

phdumair commented 4 months ago

issue

The broken line in the case is 22 (3 to 23). And the generator is only attached to 1.

My question:

  1. what's happening with the 25-29 line, initially it was opened, but was it closed after reconfiguration, as it shows a dotted line? Also, why does it not supply to node 24 23?

  2. Why did 9 15 tie switch close and the 14 15 switches get opened? Can you please explain me this?

shepardyan commented 4 months ago

Hi!

  1. This is due to the constraint on the maximum power capacity of the lines. If we assume sufficient power transmission capability for each line, bus 23/24 could be picked up.
  2. The resilience reconfiguration problem is rather intricate, with numerous influencing factors. You might consider introducing a constraint to keep the 14-15 line closed, then examine if this affects the objective function at the optimal solution.