BMU-H17 - Intermittently rebooting #165

Closed Kyle-Swanepoel closed 1 year ago

Kyle-Swanepoel commented 1 year ago

Hi,

There is still an intermittent issue with BMU-H17, fw.158 whereby the BMU reboots itself under normal operation. The SoC then halves itself.

I've also noticed this then turning the isolator ON, the BMU will reinitialize the BMSs and then close the relay.

SoC was 57% before it reset. image

image

Kyle-Swanepoel commented 1 year ago

BMU's reset twice this evening, SoC dropped to ~32% both times.

image image

platar86 commented 1 year ago
image

none of our BMU in the factory reboots? I need more info, Site configuration and any patterns when the reboot happens. Bussy building something to catch this event in the log

Kyle-Swanepoel commented 1 year ago

@platar86 What we have noticed is that most of the battery modules have v301 BMSs. The other sites with BMU-H17 have v304 BMSs. Can we test this in the factory on v301 BMSs?

platar86 commented 1 year ago

Please close if this issue is resolved or comment further.

Kyle-Swanepoel commented 1 year ago

Resolved, client caused the issue by powering the logger from one of the module bus bars.