Closed Kyle-Swanepoel closed 10 months ago
If charging amperage exceeds 60A per inverter, the inverter defaults to 10A max charging.
Hi team,
As discussed with Masud.
PV calculation is not correct on the Axpert MKS 2 units.
Another issue we have picked up on Axpert Ai is a discrepancy between the Total Set Charging Current on individual inverters vs the value on the cluster - examples attached. A soft reboot of the logger sometimes rectifies this. (Kuru 6.png)
https://drive.google.com/drive/folders/1K_n7jU5waPI4yg8Xuye_VZw8OoorCU5H?usp=sharing
About this, the inverter settings are 10A resolution except first one that is 2A, so if you have to set cluster current of 99A the first possible value that can be assigne is 90A, cluster is not allowed to round up
ng amperage exceeds 60A per inverter, the inverter defa
Please explain this in details
Hi team,
As discussed with Masud.
PV calculation is not correct on the Axpert MKS 2 units.
Another issue we have picked up on Axpert Ai is a discrepancy between the Total Set Charging Current on individual inverters vs the value on the cluster - examples attached. A soft reboot of the logger sometimes rectifies this. (Kuru 6.png)
https://drive.google.com/drive/folders/1K_n7jU5waPI4yg8Xuye_VZw8OoorCU5H?usp=sharing