Update hw.pxt to address plant overheating fatal errors #22

Closed rogerkbaker closed 5 months ago

rogerkbaker commented 5 months ago

Per DEER Support call on 2/7/2024, I am submitting this request to address plant overheating errors in models relying on hot water space heating.

Running all commercial building type/vintage/CZ combinations results in the following simulations failing:

Climate Zone Building Type Code Vintages CZ03 NRS 1995 VINTAGE CZ04 MLI 2016 THRU 2022 VINTAGES CZ06 MLI 2013 THRU 2022 VINTAGES CZ06 RT3 1975 THRU 1985 VINTAGES CZ07 MLI 2016 THRU 2022 VINTAGES CZ07 RT3 ALL VINTAGES CZ08 MLI 2008 THRU 2022 VINTAGES CZ08 RT3 ALL VINTAGES CZ09 MLI 2016 THRU 2022 VINTAGES CZ09 RT3 ALL VINTAGES CZ10 MLI 2016 THRU 2022 VINTAGES CZ10 RT3 ALL VINTAGES CZ11 RT3 1995 THRU 2001 VINTAGES CZ13 HTL 1975 VINTAGE CZ13 RT3 1995 THRU 2001 VINTAGES CZ14 RT3 1995 THRU 2001 VINTAGES CZ15 MLI 2008 THRU 2022 VINTAGES CZ15 RT3 1975 THRU 2001 VINTAGES

After inspecting the error files, it appears that the same root cause is at issue for nearly all of the models. The hot water loop that is used in each model to provide space heat to one or more zones encounters a fatal “runaway temperature” situation. This runaway temperature issue appears to occur during the summer months, where a minimal amount of space heating is required for a short period of time when transitioning from an unoccupied “setback” temperature to an occupied temperature. The amount of space heating is very small, and inspection of the hot water pump outlet temperature for one working prototype combination (MLI/2013 vintage/CZ04) shows that, during the summer months, the pump heat imparted to the working fluid exceeds the heat needed by the heating coils during this temperature recovery period. Also, the hot water loop used in the models is an “adiabatic” loop, meaning that there is zero heat loss from working fluid in the loop piping. In the one model I inspected, the hot water loop reached temperatures exceeding 240°F by early September before significant heating loads bring the loop back toward its intended 180°F setpoint. This suggests that the issue affects all models using the adiabatic hot water loop, even if only certain vintages may fail due to runaway loop temperatures. I am attaching the hourly output file that supports my conclusion; column H (pump shaft power) confirms the intermittent operation of the pump, while Column I shows the pump outlet temperature. The peak temperature for this model is achieved on Sept 14 @23:00. (output attached) instance MLI 2015 CZ4 adiabatic.xlsx

The amount of pumping energy added to the hot water loop is dictated by the hot water pump design kW and the part-load power/flow profile, as defined by the pump coefficients. The current hot water pump coefficients in hw.pxt reflect a pump that “rides the curve”; this profile injects a significant fraction of pumping energy into the working fluid even at very low flow percentages (e.g., a pump that is flowing 30% of capacity will require 61.6% of design kW). When I compare the DEER prototypes with previously-built CalBEM models as well as example commercial prototype models from the CBECC software, it appears that the latter categories of models use hot water pump coefficients that correspond to VFD pump control; with those coefficients, the same 30% flow would require only 6% of design kW. When the VSD coefficients are substituted in the hw.pxt file and models rerun, all of them successfully run, except for the 1975 Hotel/CZ13 combination, which appears to have unique issues not discussed here. I attached a spreadsheet comparing the effects of the the pump coefficients on the flow/power profile. hw.pump.coefficient.comparison.xlsx

The root cause issue here appears to be that the adiabatic hot water loop has no mechanism to accommodate ordinary heat losses. The existing loop design is consistent with the EnergyPlus Plant Application Guide, but a long-term resolution to this issue would involve substituting a length of indoor pipe, with insulation, for one of the adiabatic pipes that the Guide recommends. I was able to modify [one] idf file in such a manner by replacing an adiabatic pipe from the pump output, and this modification, if designed properly, would introduce a small heat loss from the hot water loop that more closely mirrors actual piping implementations. However, I suspect that making such modifications to the hw.pxt file would be very time-intensive, as it would require developing some method to determine the optimal heat loss and codify it within the existing Ruby code. It may also require vetting with the EnergyPlus team to ensure the appropriateness of the solution given the guidance in their existing documentation.

A more expeditious work-around, which I recommend for adoption at this time, is to replace the existing hot water pump coefficients (lines 312 to 315 of hw.pxt) with the coefficients used by CBECC and CalBEM models. The existing coefficients are:

0, !- Coefficient 1 of the Part Load Performance Curve 3.2485, !- Coefficient 2 of the Part Load Performance Curve -4.7443, !- Coefficient 3 of the Part Load Performance Curve 2.5295, !- Coefficient 4 of the Part Load Performance Curve

0.0273, !- Coefficient 1 of the Part Load Performance Curve -0.1317, !- Coefficient 2 of the Part Load Performance Curve 0.6642, !- Coefficient 3 of the Part Load Performance Curve 0.4445, !- Coefficient 4 of the Part Load Performance Curve

This modification appears to allow all prototypes to run (with the exception of the single hotel model mentioned previously), based on local testing. It does not address the adiabatic nature of the plant loop, but the heat introduced by the pump is reduced to a level where runaway loop temperatures are effectively eliminated. Additionally, the hot water pump energy is a relatively small fraction of the total energy used by the HVAC system, so using these modified coefficients should not materially affect the models’ baseline energy use. It is also consistent with the CBECC 2022 software.

Justin-DeBlois commented 5 months ago

I agree with this change as an immediate fix for the 2026 code cycle but I want to add that there is an underlying error that I think still needs continued attention from the DEER team.

Central heating coil UA sizing is failing, resulting in a UA of 1.0 W/K being assigned while the max HW flow rate is assigned based a higher rated capacity. During the annual simulation when the coil can't meet the load due to the UA being too low, the coil calls for the maximum HW flowrate to maximize delta T. The pump heat then exceeds the heat transfer across the coil (UA*DeltaT).

With properly sized UA, because of the idealized pump curve and the minimum loop flow rate of 0 gpm, the heat transfer from the coil should exceed the pump power. The riding the pump curve performance curve has a maximum of 3.25 power % / flow % ratio in Roger's calculations hw pump coefficient comparison.xlsx. For example for a pump with 40 W/gpm design power, at 1 gpm the max pump power is 130 W if it's at the very bottom of the curve. For the coil to output 130W of heat at 1 gpm would only require 0.9F Delta T across the coil.

I think this error results in the central heating coil essentially not functioning in the affected prototypes.

The warnings from CZ03 NRS 1996 are: Warning The design coil load used for UA sizing is zero for Coil:Heating:Water MZ-VAV-L2_ALT HEATING COIL ~~~ An autosize value for UA cannot be calculated ~~~ Input a value for UA, change the heating design day, or raise ~~~ the zone heating design supply air temperature ~~~ Water coil UA is set to 1 and the simulation continues.

Warning The design coil load used for UA sizing is zero for Coil:Heating:Water MZ-VAV-L1 HEATING COIL ~~~ An autosize value for UA cannot be calculated ~~~ Input a value for UA, change the heating design day, or raise ~~~ the zone heating design supply air temperature ~~~ Water coil UA is set to 1 and the simulation continues.

The Component Sizing Summary Report for Coil:Heating:Water:

<html xmlns:v="urn:schemas-microsoft-com:vml" xmlns:o="urn:schemas-microsoft-com:office:office" xmlns:x="urn:schemas-microsoft-com:office:excel" xmlns="http://www.w3.org/TR/REC-html40">

  | Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] -- | -- | -- | -- MZ-VAV-L2_ALT HEATING COIL | 30282.57 | 0.000331 | 1 MZ-VAV-L1 HEATING COIL | 31869.8 | 0.000349 | 1

amine-lazrak commented 5 months ago

@rogerkbaker your temporary proposed solution sounds reasonable and addresses the issue. As you suggested, we should revisit this at some point to figure out a permanent solution, probably implementing the heat loss through pipes you mentioned. I wonder if EnergyPlus does account for the heat added by the pump when it comes to load calculations. I would expect the loop to only request the flow rate necessary to meet the loads, considering both heat sources, the boiler and the pump.

Please add a comment next to the new curve indicating the source. Instead of deleting existing one, just comment on them as well for potential future use. I'll merge your changes right after the updates.

rogerkbaker commented 5 months ago

I added the source info to the pump curve Excel file - let me know if that is sufficient. As for how EP treats pump heat, Section 17.4.7 of the Engineering Reference confirms that all shaft power ends up as heat gain to the working fluid, via frictional heat.

amine-lazrak commented 5 months ago

@rogerkbaker since you initiated the pull request and for tracking purposes, can you add the comments directly to the hw.pxt in your pull request branch. Something like below should work:

! Original performance curve as found January 2024, source: ASHRAE 90.1 Hospital EnergyPlus example model 
!  0,                       !- Coefficient 1 of the Part Load Performance Curve
!  3.2485,                       !- Coefficient 2 of the Part Load Performance Curve
!  -4.7443,                       !- Coefficient 3 of the Part Load Performance Curve
!  2.5295,                       !- Coefficient 4 of the Part Load Performance Curve
! Updated performance curve, source: CBECC Office Large Template
  0.0273,                       !- Coefficient 1 of the Part Load Performance Curve
  -0.1317,                       !- Coefficient 2 of the Part Load Performance Curve
  0.6642,                       !- Coefficient 3 of the Part Load Performance Curve
  0.4445,                       !- Coefficient 4 of the Part Load Performance Curve

Yes, there's always heat added to the fluid even if the pump parameter Fraction of Motor Inefficiencies to Fluid Stream is set to zero. However, I'm not sure how EnergyPlus identifies the main heat source, boiler runtime, and flow rate necessary to meet the loads on the demand side. If EnergyPlus accounts for pump heat gains before determining the flow rate and runtime, then I wouldn't expect this issue to occur.