The SEL plugin requires modifications #12

Closed Uffel3 closed 7 months ago

Uffel3 commented 7 months ago

The SEL plugin is great to automatically subscribe three phase current and voltage SV from a merging unit in the Subscriber Editor. However, voltage inputs VAZ and VBZ are single phase voltages from different MU's. At the moment, I have to

  1. connect MU1 to VAZ which automatically maps VCZ and VCZ as well.
  2. Unmap VBZ and VCZ
  3. connect MU2 to VBZ which automatically maps VCZ
  4. Unmap VCZ
  5. open the Supervision editor and re-map LSVS to the correct publishers.

We can either improve the SEL plugin, or I need to write detailed instructions on how to handle SEL-411L-2 relay SV subscriptions. Thoughts?

danyill commented 7 months ago

You can remove the automatic modifications by either disabling the specific plugin or:

image

Is this sufficient?

Uffel3 commented 7 months ago

Ok, I accept. The Prot 1 Engineering guide needs a bit more explanation/guidance in how to manage the SEL-411L-2.