Closed SimonYoungtree closed 9 months ago
The system will take the full hour to get to the target SOC instead of going there as fast as possible. This is done not to stress the system more than needed and to be in line with what is intended with the energy pricing concept. Imagine all of our users start dumping in the first 15 minutes of the hour and not doing anything for the rest of the hour.
Looking at yesterdays vrmlogger data of your site, you can see that the target almost always gets reached at the end of the hour.
Contact Details
siempoot@gmail.com
VRM portal ID
c0619ab31cc4
Country / region
Netherlands (nl)
B max
40
TB max
not relevant
FB max
not relevant
TG max
not relevant
FG max
not relevant
Battery costs
not relevant
Buy price
not relevant
Sell price
not relevant
feed-in possible
None
feed-in possible
None
Version
0.1.3
What happened?
A bug may have happened:
The system is still not charging with maximum power (i would expect 6kW from the Multiplusses and 1.4kW from DC). I am at the latest version, and the proper battery capacity is in (40). I do not know if this is on purpose (to incur less losses from the Multiplus (3x)) or that something is wrong