Closed maxpd1 closed 9 months ago
My assumption is that a missing Settings -> DVCC -> Controlling BMS Settings -> System Setup -> Battery monitor
did cause this problem.
The above values are getting removed either if I turn of Victron/Seplos battery or if I plug out the USB cables that this is causing the removing of the Controlling BMS as well as the Battery Monitor during the next restart.
Hi,
it is now the third time I look into my Venus OS on my Raspberry and I see the battery SOC is below Minimum SOC.
Minimum SOC is set to 10%. As I had a look into Venus it was 6% and still powering the house (there was no power outage meanwhile which would request Victron to power AC-OUT. Here only a Raspberry is powered during the latest Min SOC breakage). I changed Min SOC to 5% to have a new limitation but it went further down to 4% only to charge up from this point to the requested 5 %.
I used Venus 3.12 Raspberry connected via RS485 to a Seplos BMS with serialbattery as batterymonitor. ESS mode: Optimized without battery life DVCC activated
Regards maxpd