SolaX X1-Hybrid G3 HV-5.0T #4

Closed siralexbox closed 4 years ago

siralexbox commented 4 years ago

Great work, Nothing happens when I change Work Mode, Charger max current, Discharge max and Min capacity. Also I cant find the Load/Generator register. Using solax_x1_hybrid_g3_triplepower.yaml on a X1-Hybrid G3 HV-5.0T

mfcltd commented 4 years ago

Have you enabled remote control on your Inverter? I had to do this when using RS485.

siralexbox commented 4 years ago

Upss, done, was the remote control option. Thanks

siralexbox commented 4 years ago

Bu still cant find the "load/generator" value, is this calculated from the other values? Or is there a register just for it?

wills106 commented 4 years ago

The load / generator is "SolaX Measured Power" register 70.

siralexbox commented 4 years ago

Isn't register 70 the Feed in Power? On the solax app there are different values for injected power and home load. I have the power meter installed, to allow zero injection, is the home load value coming from this meter? Can you point me to the registers list. Thanks

wills106 commented 4 years ago

As per the comment: # Negative pulling from Grid, Positive exporting to the Grid

My setup uses a Eastron SDM230-ModBus energy meter.

There is no official register list available from SolaX

wills106 commented 4 years ago