Hello Zacs, thanks for the good work, I really like the functionality of this dual mode thermostat. Unfortunately, it doesn't work for me. I think I have identified a bug, but I'm very surprised t be alone with this problem, so maybe the problem is "me" :-) ...
This is what's happening:
Room temp: 23
Heat mode: target temp set at 24 => the heating will start... target temp set at 20 => the heating will stop. All good!
Cool mode: target temp set at 22 => the cooling will start... target temp set at 24 => the heating will stop. All good!
Auto mode: (this is where it becomes ticky):
Lower temp set at 24: the heating will start... Lower temp set at 20 => the heating will NOT stop. In the logs, it seems that it tries to stop the AC, not the heater
Higher temp set at 22: the cooling will start... Higher temp set at 24 => the cooling will stop.
So it appears that the issue is only when in Auto mode, and only with the heater not being stopped when the temp is reached.
Hello Zacs, thanks for the good work, I really like the functionality of this dual mode thermostat. Unfortunately, it doesn't work for me. I think I have identified a bug, but I'm very surprised t be alone with this problem, so maybe the problem is "me" :-) ... This is what's happening:
I hope it's clear... Is this a known bug? Thanks!