This component will let you monitor (sensors, binary sensors and text sensors) and control (numbers and selects) compatible inverter without need of installing Chinese software and depend on any third-party services.
output_frequency
, warning_buzzer
, inverter_maximum_power
.battery_charge_cut_off_current
, output_voltage
, total_charge_current
, util_charge_current
. You can set tham as any number from the range in comparison to inverter's menu where you can only select values from predefined options.uart:
- baud_rate: 9600
inv_8851:
version: 1 # read about this parameter below
sensor:
- platform: inv_8851
battery_voltage:
name: "Battery voltage"
...
Full list of available entities is here.
There are several options you may need to set:
update_interval
version
update_interval
tells how often to request state and configuration from inverter, default value is 5s and should suite most situations.
inv_8851:
update_interval: 30s
version
should be one of 1
(confirmed firmware version: 0005) or 2
(confirmed firmware version: 8100). Right now there are several protocol versions. They are pretty similar except they have a bit different packets length. 144/90
bytes for version=1 and 148/94
bytes for version=2 (state and config data block length respectively). If you experience problems with changing parameters it could mean that you should try other value (you can use substitutions→version
parameter). It's only my guess, but it looks like version 1 is not compatible with newer firmware, so try using version 2 for newer models. Also you should see warning messages in logs if you peaked wrong version.
24v and 48v files are different only in configuration of some entities witch has no sense for 24v version (bms_cell_09_voltage — bms_cell_16_voltage) and minimum/maximum values for some number entities (as they depend on voltage). So in theory flashing "wrong" configuration shouldn't make any harm to ESP or inverter.
This project build to be as simple is possible, so in most cases you woudn't need those files. Regular .yaml
file will download latest stable version from this repository and use it upon build process. But if you want to customize configuration or you plan to change files in packages
or components
directories, than you probably want to use those.
First of all there are two places you can find inverter_maximum_power
parameter:
substitutions
section of example filesnumber
configuration sectionThe reason for that parameter present in substitutions
section is to limit max_value
parameter for inverter_maximum_power
number entity. This is needed to prevent user from setting to high value for that entity.
Number entity inverter_maximum_power
sets software limitaion for inverter's maximum power (total power inverter consumes from grid including battery charging power). Setting value that is higher than factory-default (4500W for 4.5kW inverter version and 6500W for 6.5kW inverter version) for that number entity can lead to potential damage. From other hand you can set software limitaion lower than factory-default to protect your inverter from working in conditions close to maximum possible and prolong it's life. In case of exceeding 110% of inverter_maximum_power
value, inverter will turn off with error code of 07
.
Please make sure you understand what you're doing before adjusting this parameter.
You can flash WBS1-V001 using this component (use corresponding dtu-wbs1-v001...-example.yaml
file). This way you can use original DTU with much more comfortable and easy way. This configuration also supports onboard LED indication.
In order to flash original DTU follow next steps:
COM1
with valid port number):esptool.exe -p COM1 -b 460800 read_flash 0x0 0x400000 DTU.bin
COM1
and DTU.bin
with valid port number and firmware dump file backed up in step 4 path):esptool.exe -p COM1 -b 460800 write_flash 0x0 DTU.bin
You can flash ESP32 or ESP8266 using this component the same way you flash your other ESPHome projects. Read official guides if you have any questions.
ID | Description | Unit | Res. |
---|---|---|---|
battery_charge_current | Maximum current to charge battery. It will start decreasing when battery enter absorption stage. | A | 0.1 |
battery_voltage | V | 0.01 | |
bms_battery_current | A | 0.1 | |
bms_battery_soc | % | 1 | |
bms_battery_voltage | V | 0.01 | |
bms_cell_01_voltage | V | 0.01 | |
bms_cell_02_voltage | V | 0.01 | |
bms_cell_03_voltage | V | 0.01 | |
bms_cell_04_voltage | V | 0.01 | |
bms_cell_05_voltage | V | 0.01 | |
bms_cell_06_voltage | V | 0.01 | |
bms_cell_07_voltage | V | 0.01 | |
bms_cell_08_voltage | V | 0.01 | |
bms_cell_09_voltage | V | 0.01 | |
bms_cell_10_voltage | V | 0.01 | |
bms_cell_11_voltage | V | 0.01 | |
bms_cell_12_voltage | V | 0.01 | |
bms_cell_13_voltage | V | 0.01 | |
bms_cell_14_voltage | V | 0.01 | |
bms_cell_15_voltage | V | 0.01 | |
bms_cell_16_voltage | V | 0.01 | |
bts_temperature | °C | 1 | |
bus_voltage | V | 0.1 | |
fan1_speed_percentage | % | 1 | |
fan2_speed_percentage | % | 1 | |
grid_current | A | 0.01 | |
grid_frequency | Hz | 0.01 | |
grid_voltage | V | 0.1 | |
inverter_apparent_power | VA | 1 | |
inverter_apparent_power_percentage | % | 1 | |
inverter_current | A | 0.01 | |
inverter_frequency | Hz | 0.01 | |
inverter_power_percentage | % | 1 | |
inverter_software_version | N/A | 1 | |
inverter_voltage | V | 0.1 | |
inverter_voltage_dc_component | ? | ? | |
load_apparent_power | VA | 1 | |
load_current | A | 0.01 | |
load_power | W | 1 | |
log_number | N/A | 1 | |
low_load_current | A | 0.01 | |
ntc2_temperature | °C | 1 | |
ntc3_temperature | °C | 1 | |
ntc4_temperature | °C | 1 | |
parallel_current | A | 0.01 | |
parallel_frequency | Hz | 0.01 | |
parallel_voltage | V | 0.1 | |
pv_current | A | 0.01 | |
pv_power | W | 1 | |
pv_voltage | V | 0.1 |
ID | Description |
---|---|
battery | Indicates if battery is connected |
buck_topology_initialization | Indicates if buck topology is initialized |
bus | ? |
bus_and_grid_voltage_match | ? |
charging | Indicates if battery is still charging |
disable_utility | ? Indicates if inverter works in bypass mode |
equalization_finished | Indicates if battery equalization program is finished |
equalization_started | Indicates if battery equalization program is started |
float_charging | Indeicates if battery is in float charging mode |
grid_pll | Indicates if inverter phase is locked |
inverter_topology_initialization | Indicates if inverter's topology is initialized |
llc_topology_initialization | Indicates if LLC topology is initialized |
parallel_lock_phase | Indicates if phases of inverters connected in parallel are locked |
pv_excess | Indicates if there is PV power excess avaiable |
pv_input | Indicates if PV is connected |
pv_topology_initialization | Indicates if PV topology is initialized |
system_initialization | Indicates if all inverter's systems are initialized |
system_power | Indicates if inverter is turned on using button on left side |
ID | Description |
---|---|
buck_topology | Buck topology state |
inverter_topology | Inverter topology state |
llc_topology | LLC topology state |
pv_topology | PV topology state |
ID | Description | Options | Menu |
---|---|---|---|
auto_return | Auto return to home screen after 1 minute of inactivity | OFF ON |
19 |
backlight | Backlight always ON mode | OFF ON |
20 |
battery_equalization | Battery equalization program activation | OFF ON |
33 |
battery_type | Battery type selection. If User-defined type is selected, then additional voltage parameters can be set. | AGM Flooded User-defined Library |
05 |
buzzer | Buzzer that beep every time you press any screen button | OFF ON |
18 |
charge_energy_priority | Charger source priority | PV & Grid — PV and Grid at the same time PV > Grid — Priority for PV, then Grid PV only — Only PV |
16 |
fault_record | Record fault code | OFF ON |
25 |
frequency | Default frequency output mode, can be adjusted with output_frequency number |
50Hz 60Hz |
09 |
grid_voltage_range | Grid voltage range in witch inverter will work, otherwise will switch to battery | APL — 90-265V UPS — 170-265V |
03 |
on_grid | Send produced enery to Grid | OFF ON |
10 |
output_energy_priority | Which source to use first: Grid or PV | PV > Grid > Battery — Grid over battery PV > Battery > Grid — Battery over grid |
01 |
overload_restart | Automatic restart after overload protection | OFF ON |
06 |
overtemp_restart | Automatic restart after over temperature protection | OFF ON |
07 |
parallel_operation | Parallel operation mode | OFF ON |
14 |
phase | Witch phase inverter is connected to | A B C |
15 |
power_buzzer | Buzzer that beep every time Grid becomes unavailable | OFF ON |
22 |
powersave_mode | Power save mode, will pulse output voltage to determine and start if load is connected | OFF ON |
04 |
warning_buzzer | Buzzer that beep every time inverter raise warning | OFF ON |
N/A |
ID | Description | Unit | Res. | Range | Menu |
---|---|---|---|---|---|
battery_back_to_util_voltage | Voltage point at witch inverter will switch to Grid in PV > Battery > Grid mode | V | 0.1 | 20…29.2 40…58.4 |
13 |
battery_bulk_voltage | Fully charged battery voltage | V | 0.1 | 24…29.2 48…58.4 |
26 |
battery_float_voltage | Floating charging mode voltage | V | 0.1 | 24…29.2 48…58.4 |
27 |
battery_charge_cut_off_current | Charge current at witch inverted assumes that battery is fully charged and switches into floating charging mode | A | 0.1 | 2…20 | 12 |
battery_cut_off_voltage | Minimum battery voltage, inverter will disconnect battery at this point | V | 0.1 | 20…24 40…48 |
29 |
battery_equalization_interval | How often battery equalization program will be triggered | Day | 1 | 0…90 | 37 |
battery_equalization_time | How long battery equalization program will run | Min. | 1 | 5…900 | 35 |
battery_equalization_timeout | How long battery equalization program can run before terminating | Min. | 1 | 5…900 | 36 |
battery_equalization_voltage | Battery equalization voltage | V | 0.1 | 25…29.5 50…59 |
34 |
inverter_maximum_power | Inverter maximum output power | W | 1 | 0…4500 0…6500 |
N/A |
output_frequency | Output frequency, that can be in range 50-55Hz for 50Hz mode and 60-55Hz for 60Hz mode | Hz | 1 | 50…55 60…55 |
N/A |
output_voltage | Output voltage, resets to closest lower number that is multiple of 5 (234V → 230V, 229V → 225V) after exiting menu | V | 1 | 100…240 | 08 |
total_charge_current | Maximum battery charge current equals PV current + Grid current | A | 0.1 | 0…130 0…150 |
02 |
util_charge_current | Maximum current used from Grid to charge battery | A | 0.1 | 0…110 0…140 |
11 |
Here you can find original firmware dump file. Restore procedure described in the last step of Flashing DTU WBS1-V001 section.